  1. GENERAL                                       

 

Generally, leakage current clamp testers are used to supervise the insulated conditions 
in AC low voltage circuit. Those leakage clamp testers can measure the leakage current   
of grounding line without cutting off the electricity of low voltage circuit on live power 
condition. 
 
Nowadays, however, many harmonics and high-frequency currents are contained to 
leakage  current  of  grounding  line  due  to  an  increase  in  high-frequency  electric 
appliances with inverter, etc. and the measured values by different instruments are not 
same even at the same measuring point. 
 
Also, leakage current contains the resistive component (Ior) which flows to the ground 
by insulation resistance and the capacitive component (Ioc) which flows by electrostatic 
capacity. The actual insulation deterioration is caused by Ior but normal leakage clamp 
testers cannot judge what kind of leakage current is flowing. 
 
Under the circumstances, there are two kinds of instruments : 
(1)

 

Igr measuring apparatus with low frequency injection method. 

(2)

 

Ior measuring apparatus with simplified effective method. 

 
In  the  low  frequency  injection  method,  a  certain  frequency  different  from  50/60Hz  is 
piled up by the injection transformer and then, the in-phase current is extracted from 
the following current. This apparatus is inconvenient to carry and is very expensive. 
 
On the other hand, in the simplified effective method, Ior is measured by extracting the   
in-phase component from leakage current based on the voltage phase. This method 
cannot detect the insulation condition of grounding phase and it is getting difficult to 
take the voltage phase in recent transformation facilities and in the circuit of 3 phase/ 
3  wires,  it  is  not  reliable  due  to  the  error  caused  from  unbalance  capacitance  to  the 
earth.   
 
Our newly developed Ior clamp tester does not need the voltage input and can measure 
Ior values of the grounding line as well as the lines of feeder simply by clamping CT. 
Model MCL-400IR is the first and epoch-making leakage clamp tester. 
   
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for MCL-400IR

Page 1: ...ad this instruction manual completely and familiarize yourself thoroughly with all functions Keep this instruction manual carefully to take out whenever you need MULTI MEASURING INSTRUMENTS CO LTD Aki...

Page 2: ...or storage this instrument where the mechanical vibration can be directly transmitted as it may cause defect of the instrument Do not use this instrument nearby the appliances which generate strong ma...

Page 3: ...ircumstances there are two kinds of instruments 1 Igr measuring apparatus with low frequency injection method 2 Ior measuring apparatus with simplified effective method In the low frequency injection...

Page 4: ...side of unloading transformer The ratio of the 5th and 7th harmonic voltage at the low voltage side influenced from the high voltage lines is almost fixed Consequently the compositions of the 5th and...

Page 5: ...nge Selection Rotary Switch Input Frequency 45 60Hz AC Conversion RMS Detection Method A D Conversion Double Integration Method Display 3 3 4 digit LCD max reading of 4000 Sampling Rate 2 times second...

Page 6: ...al 1 Batteries 3 installed into the instrument 3 2 ELECTRICAL CHARACTERIC 23 5 less than 80 RH Range Resolution Accuracy AC40mA 0 01mA 1 rdg 8dgt AC400mA 0 1mA AC4A 0 001A AC40A 0 01A AC300A 0 1A 1 rd...

Page 7: ...Switch Manual range switch for the selection of current 40mA 400mA 4A 40A 300A and voltage 500V Data Hold Switch By press one time DH sign will be displayed on LCD and the displayed value will be hel...

Page 8: ...this switch the calculation will start and Wait mark is lightening on the display until the calculation had been finished After that Ior value will be displayed The displayed value before calculation...

Page 9: ...re the line current MEASUREMENT OF LEAKAGE CURRENT 1 Measurement for leakage current of grounding line Same procedure as for the measurement of line current 2 Except for grounding line The operation i...

Page 10: ...current measurement Except for the grounding line In case of single phase two or three wires clamp CT to two wires or three wires together Setting of circuit is 1 Ir by Ior SELECT switch In case of t...

Page 11: ...test leads MEASUREMENT OF HARMONICS VOLTAGE Refer to the operation of MEASUREMENT OF HARMONICS CURRENT But the measuring method is same as MEASUREMENT OF VOLTAGE WARNING It may cause electric shock Ch...

Page 12: ...d It may cause liquid leakage of batteries and may cause the damage to the instrument When the batteries get exhausted and voltage is getting below than the operation Voltage sign will appear on the d...

Page 13: ...contact the dealer where you bought the instrument The warranty period is 12 months from the date of purchase and the instrument shall be repaired at free of charge provided that we judge the cause of...

Page 14: ...lation deterioration of grounding phase In case that the mark is lightening on off during the measurement of resistive leakage current Ior the instrument is detecting the insulation deterioration of g...

Reviews: