background image

7

Disassembly / Reassembly Instructions

HG-8 COLD CLIMATE FLUSHING SYSTEM

       TOOLS NEEDED: 

Philips screwdriver, flat-head screwdriver, HG-20087 T-handle wrench

HG-8 DISASSEMBLY AND REASSEMBLY INSTRUCTIONS

4.

 To prevent the loss of the 

solenoid plunger and spring, 
place an object or have a finger 
over the plunger of the solenoid. 
Allow the plunger enough space 
to kick out of the solenoid body 
into the object or finger hovering 
over it.

5.

 If test is successful, return the 

flush / meter assembly to its 
operating position below grade.

6.

 Return insulation pad and cast 

iron meter lid to their 
proper positions.

If everything checks out,  
the electrical system is in  
working order.
Valve Disassembly and Check
1. 

Remove six (6) bolts from 

top cover.

2. 

Slowly pull cover off the valve.

3. 

Remove rubber diaphragm and 

inspect for holes or worn areas.

4. 

Be certain to avoid contacting 

the EPDM rubber diaphragm 
with pipe putty. Pipe putty can 
cause the rubber to thin out and 
leak.

5. 

Remove the valve screen plug on 

the lower half of the valve body. 
Be careful not to exert too much 
force when pulling plug out.

6. 

Check for debris in the valve 

screen on the inlet side with the 
lower half of the valve body by 
removing the valve screen plug.

7. 

Return valve plug to its 

proper location when debris 
screen is cleared.

8. 

Replace the top cover back onto 

the diaphragm – make sure to 
line up the openings in both.

9. 

Match up the top cover of the valve 

with the bottom portion. The arrows 
have to align on both portions.

10. 

Replace the bolts and 

  tighten down.

Although the Hydro-Guard HG-8 
Cold Climate Sub-Surface Unit was 
delivered completely assembled, it 
may be necessary and/or desirable 
to disassemble portions of the 
Unit, or the Unit in its entirety, in 
order to allow for required service 
and maintenance. If disassembly 
is necessary, please follow the 
directions below. Always close the 
curb stop before working on the 
unit.

Disassembly
1.

 Shut off water supply to the  

unit and remove the green 
housing cover.

2.

 Remove the composite or 

cast iron lid of HG-8 protective 
ground sleeve.

3.

 Remove foam insulation pad.

4.

 Using the lifting holes and/or 

lifting strap in the steel platform, 
raise the flushing system meter 
assembly to top of meter box 
and lock into place.

5.

 Modular design of valve and 

double check valve allow for 
service to be completed without 
removal of the devices’ bodies 
from the piping assembly.

Electrical System Check
1. 

Pull internals of HG-8 to top of 

PVC in-ground protective housing 
and lock into place.

2.

 Unscrew solenoid from valve – be 

careful to not drop the 
solenoid plunger and spring into 
in-ground housing.

3. 

Using the TBOS-II handheld, 

connect the infrared connector of 
the handheld to the antenna on 
the controller interface mounted 
inside of the device. Using 
the programming keys of the 
handheld run a 2 minute manual 
flush sequence. 

NOTE: Plunger inside solenoid 
should be down when running and 
up when off.

WARNING: Avoid overuse of 
pipe sealant and never allow 
sealant to come into contact 
with EPDM rubber diaphram. 

Reassembly
1. 

If any disassembly has been 

conducted of the control valve 
and/or double check valve, 
verify that all bolts are properly 
tightened. Check assemblies  
for leakage prior to lowering 
flushing / metering assembly back 
into position below grade.

2. 

Using lifting holes and/or  

lifting strap on steel plate, lower 
flushing / metering assembly 
below grade by slowly lowering the 
steel mounting plate to the lower 
part of the in-ground protective 
housing (DO NOT apply excessive 
force to assembly).

3. 

Turn water supply to the unit 

on. Using the TBOS-II handheld 
controller, run a two minute 
manual flushing procedure to 
confirm all components are 
operational.

4.

 Return insulation pad and cast 

iron lid to their proper location.

!

Summary of Contents for Hydro-Guard HG-8 Cold Climate

Page 1: ...by Mueller Co only and may not be applicable for any other use 2 DO NOT exceed the pressure ratings of any components or equipment Exceeding the rated pressure may result in serious injury and or pro...

Page 2: ...e storm pond etc The meter and flushing assembly can be raised for maintenance and repair and then lowered back down into the box below the frost line A medium density foam insulation pad freeze prote...

Page 3: ...w existing grade and ensure the meter lid is level with existing grade 7 Place the pit in the excavated area and connect the inlet piping Hand tighten the fitting to the pit then turn two full turns w...

Page 4: ...te the device list can be found on the label located on the back of the controller housing with the designation Default name The App will indicate that it is in the process of connecting 8 Once the de...

Page 5: ...controller 3 Make sure no water is inside battery compartment 4 Screw the NODE rear body back onto front half NOTE Make sure that seal marker on rear half of the NODE lines up with front half ensuring...

Page 6: ...time in 15 minute increments 4 Press RIGHT ARROW key to add an additional START TIME to program displayed The start time number is shown in upper left corner of display 5 Press PRG key to add START T...

Page 7: ...intenance If disassembly is necessary please follow the directions below Always close the curb stop before working on the unit Disassembly 1 Shut off water supply to the unit and remove the green hous...

Page 8: ...or lack of connection Run a manual flush and confirm the solenoid plunger is kicking out and pulling back in by listening for a click Check connections for corrosion breaks or lack of connection Chec...

Page 9: ...d until snug The following is a brief overview and introduction to our options Integrated Sample Station The HG 8 Cold Climate Sub Surface Discharge Unit features a Sample Port quick connect that allo...

Page 10: ...ine Dechlorination Assembly 10 HG FP100 Thermal Control Valve 11 546138 100 1 Backflow Double Check Valve 12 014215 330N 1 Meter Coupling 13 024265 1 330N 1 Ball Angle Meter Valve 14 014210 1 330N 1 M...

Page 11: ...11 Notes HG 8 COLD CLIMATE FLUSHING SYSTEM...

Page 12: ...are liable only for their own acts and omissions and not those of each other MWP brands include Mueller Echologics Hydro Gate Hydro Guard HYMAX Jones Krausz Mi Net Milliken Pratt Pratt Industrial Sing...

Reviews: