background image

These instructions apply to this sleeve when used with 

Mueller mechanical joint cut-in valve.

 

Use this Gasket on the spigot (opposite) end of sleeve – 

Set other side of tag.

 

Take one gasket from cut-in valve – Use it in this end. 

Instructions below.

 

This sleeve and valve fit two diameters of cast iron 

pipe, using two diameters of End Gaskets. Be sure 

End Gaskets with Cut-in Valve are right for the outside 

diameter of your existing piping or main. See information 

in end of valve.

 

Determine location of valve on main by dimen. “A” in

table on other side of tag. Measure and mark off 

dimension “L” from the table and clean pipe thoroughly 

as shown. This can be done best before cutting the 

main. First shut off main, then cut off “L” length of pipe 

(as shown in table) out of the main. Slide the Pipe Glands 

and End Gaskets, taken from Valve, over each end of 

cut main. Back Stop Screw in sleeve out 3/4” and slide 

sleeve over main. Slide a Pipe Gland and a duck-tipped, 

rubber End Gasket over sleeve spigot. Position valve on 

end of main. Slide sleeve spigot in end of valve. Screw 

stop screw into sleeve with a wrench until tight. Position 

all three end gaskets and pipe glands. Gaskets wetted 

with a soapy water solution install more easily. Install 

all gland bolts and with wrench, tighten alternately 

(180° apart) until all are evenly tight. 90ft. lbs. max. 

torque. Open cut-in valve. Installation is complete. 

Turn on pressure in main.

Installation Instructions

MJ Cut-In

Valve

(continued)