150402 – LO Oil Refill
Yellow alarm. Initiated by SAM.
Cause
Corrective action
No oil replenishment within a
configurable time.
u
Check oil replenishment system.
150403 – AL Oil Refill Error
Red alarm. Initiated by SAM.
Cause
Corrective action
After initiation of the alarms
“HI Oil Refill” and
“HI Lube Oil Level refill” a
configurable time-out period
starts. When this time-out
period is expired, the engine is
stopped.
1. Check engine oil level (→ Page 162).
2. Check oil supply (→ Page 162).
150410 – MD/SD MesPower
Red alarm. Initiated by SAM.
Cause
Corrective action
Actual power signal out of valid
range.
1. Check cabling.
2. Check signal.
150504 – LO Engine Power
Yellow alarm. Initiated by SAM.
Cause
Corrective action
The engine is running below
minimum load.
u
Check power setpoint signal.
150601 – AL Gas Valve 1 feedback
Red alarm. Initiated by SAM.
Cause
Corrective action
Feedback signal from valve 1
does not correspond with
setpoint signal.
u
Check valve 1 and cabling.
150902 – SS Local Initiated Emerg. Stop
Red alarm. Initiated by SAM.
Cause
Corrective action
Emergency stop detected.
Emergency stop was released
manually (button), or ignition
system reported overspeed.
u
76 | Troubleshooting | MS150057/02E 2013-10
TIM-ID: 0000017543 - 001