![MTU 10V2000Mx4 Operating Instructions Manual Download Page 52](http://html1.mh-extra.com/html/mtu/10v2000mx4/10v2000mx4_operating-instructions-manual_1852617052.webp)
5.7 Fuel treatment system – Switching on
Preconditions
☑
The on-board power supply is switched on.
NOTICE
Risk of damage to engine/system.
Risk of severe damage to property!
• Before switching on, ensure that the engine/system is ready for operation.
• Before switching on, ensure that all housings are closed.
• Before switching on, ensure that no work is in progress anywhere on the entire system.
Fuel treatment system – Switching on
1.
Carry out checks prior to start-up (→ Page 48).
2.
Switch on master switch on switchgear cabinet.
Result:
Signal lamp “Control voltage present” lights up.
3.
Switch on switch for pump.
Result:
Signal lamp “Pump running” lights up.
52 | Operation | MS150060/04E 2016-02
TIM-ID: 0000007731 - 006