MTT MS3727 User Manual Download Page 2

  User's Manual 

MS3727 

Slim Plug-In Signal Selector 

 

Rev. 1.50 

 
 

 

 
On Wiring: 

  Connections to the instrument should be made to the terminal 

block. For assignment of the terminals, refer to section 6. The 
recommended screwing torque is 0.8 to 1.0 Nm. 

  For lead wires, use a highly flexible stranded conductor. The 

recommended nominal cross-section of the lead wire conductor 
is 0.5 to 2.0 mm

2

  The connection of the lead wire to the terminal block should be 

made with the insulated crimp terminal attached to the end of the 
wire. Without the insulation, short circuit or electric shock may 
occur. The recommended thickness of the crimp terminal is 0.7 
to 1.0 mm. 
Note that only up to two (2) crimp terminals can be connected to 
one (1) terminal screw. In this case, the thickness of the crimp 
terminal should be not greater than 0.8 mm.

 

 

φ3.7

6.8

 m

ax

.

3.4 max.

4.6 min.

 

 

To Avoid Erroneous Measurements: 

  In order to reduce the influence of noise, the input/output wire 

and power supply wire should not be used in a same bundle or 
same conduit. They should be installed separately with a 
minimum distance of 200 mm. 

 Avoid wiring the signal lines in the vicinity of equipment 

generating magnetic fields or electromagnetic waves, such as 
electric motors and large-scale transformers. If inevitable, 
anti-noise measures such as employment of shielded wires are 
indispensable. 

  At least 30 minutes of warm-up is required prior to operation. 

  Any sensor or equipment to be connected to the instrument 

should be selected in consideration of the input/output 
impedance of the same. (For detailed specifications, refer to 
section 4 or the relevant product specification sheet that can be 
downloaded from our website at https://www.mtt.co.jp.) 

 
 

4. About the Product

 

The MS3727 switches between two DC voltage or current input 
signals by switching input.

 

 

Features: 

  Pin and socket contacts are gold-plated (0.2

μ

m) to ensure high 

reliability and long-term stability. 

  High dielectric strength of 2,000 VAC between input, [output 1, 

output 2], power, and ground. 

  The power unit can deliver AC power ranging from 85 to 264V 

steplessly without switching to meet varied power requirements. 

  Plug-in type for better maintainability 

  Drop-proof terminal screws for ease and safety of installation 

  Fuse installed in the power line as standard. 

 

Specifications 

 

Input Signal 

2 channels (INPUT-1, INPUT-2) 

 

Shunt Resistor 

DC current signal (shunt resistor 50

Ω

): Built in   

Allowable Input 
Range 

DC current input: ±50mA max. 

(Minimum span: 1mA) 

 

DC voltage input: ±50V max. 

(Minimum span: 10mV) 

 

Switching Input 

Dry contact (Internal pull-up: 24 VDC @ 10mA)   

Output Signal 

DC current signal or DC voltage signal: 
Equivalent to the input signal level 
DC current signal (shunt resistor 50

Ω

): Input 

signal × shunt resistor (50

Ω

Note: Either INPUT-1 or INPUT-2 is output. 

 

Operation 

When the power is ON and the switching input 
is ON, INPUT-1 is output. 
When the power is ON and the switching input 
is OFF, INPUT-2 is output. 
When the power is OFF, both INPUT-1 and 
INPUT-2 give no output. 

 

Accuracy Rating 

DC current signal (shunt resistor 50

Ω

): ±0.1% 

(accuracy of shunt resistor) 

 

Temperature 
Effect 

DC current signal (shunt resistor 50

Ω

): 

±25ppm/°C 

 

Response Time  5ms max. 

 

Internal 
Resistance 
between Input 
and Output 

50

Ω

 max. per wire 

(ON resistance of photo MOS relay) 

 

Condition of 
Non-selected 
Input Channel 

DC voltage input: Open (leakage current 1µA 
max.) 
DC current input: 50

Ω

 max. (due to the ON 

resistance of photo MOS relay) 
DC current input (shunt resistor 50

Ω

): Shunt 

resistor 50

Ω

 

Note: When the power is off, the 
above-described condition applies to both 
channels. 

 

Insulation 
Resistance 

100M

Ω

 min. (@ 500V DC) between [input, 

output], switching input, power, and ground. 

 

Dielectric 
Strength 

[Input, Output] / Switching Input / [Power, 
Ground]: 2000V AC for 1 minute (Cutoff 
current: 0.5mA) 
Power / Ground: 2000V AC for 1 minute (Cutoff 
current: 5mA) 

 

Surge Withstand 
Capability 

Tested as per ANSI/IEEE C37.90.1-1989. 

 

Storage 
Temperature 

-10 to 60°C 

 