Slim Plug-In Distributor with Isolated Single/Dual Output 

 

Rev. 1.70 

5. External Dimensions & Terminal Assignments

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

6. Terminal Connection Diagram 

   When used as a distributor:       When used as an isolator: 
        (Ex switch: ON)                                    (Ex switch: OFF) 
 

Terminal

No.

Terminal

No.

 

 

Note: For the single output model, the OUTPUT2 shown should be 

interpreted as N.C. 

 
When using the instrument as an isolator, be sure to turn off the 
transmitter power switch (see below). 
 

Function

Transmitter

Power

Ex Switch

Distributor

Isolator

* Switch lamp is on.

* Switch lamp is off.

Ex Switch

 

 
If the transmitter power switch remains on, the following incidents 
may occur. 
 
1.  If terminals #9 and #10 are connected, the 24VDC power will be 

short-circuited to the ground through the internal input resistor 
(250

). This may cause the resistor to burn out. 

2.  If terminals #9 and #11 are connected, the 24VDC power will be 

short-circuited directly to the ground. This may cause damage to 
the power circuit. 

3.  If terminal #9 is connected to the receiving instrument, 24VDC 

will be applied to the receiving instrument. This may cause 
damage to that instrument. 

Note: In both of the above cases 1 and 2, a short-term faulty 

connection may not cause any problem. If the faulty 
connection is kept for more than one hour, the problem 
described will occur. 

 

7. Terminal Connection 

The following steps should be taken prior to the connection. 
 

 

 
 
 
 
 
 
 

8. Power Line Connection 

The terminals for power supply connection (

 and 

) are covered 

with a plastic plate for safety (see Fig. 1). 
Open the cover plate and connect the power lines to the terminals 
(see Fig. 2). 
Return the cover plate to its original position (see Fig. 3). 
 

4

5

1

2

P/+

N/-

4

5

4

5

Terminal Block
Cover

 

 
 
Note: For your safety, do not make any electrical connections or 

disconnections with power supplied to the instrument. Make 
sure that all terminal screws are properly tightened each time 
you finish the tightening. 

 
 

(1) Loosen the terminal screw. 

(2) Insert the tip of a 

screwdriver bit beneath 

the washer and push it 

up to make ample room 

to receive a cable.

 

Fig. 1 

Fig. 2 

Fig. 3 

Transmitter power switch

ZERO Trimmer

SPAN Trimmer

Screw hole for

wall mounting

Screw hole for wall mounting

Fixing screw