If the magnet leaves the defined measuring range of the sensor, the system will indi-
cate the following outputs:
1. If the magnet leaves the measuring range moving towards the end of the sensor
rod, the output voltage will be NEGATIVE.
2. If the magnet leaves the measuring range moving toward the electronics head of
the sensor, the output will be a co10V.
8.2 Operation Mode 2 (Programmable Adjustment)
The analog output configuration can be set-up by defining the desired output range of
the sensor with two set-points (SP1 and SP2).
Switch S1 = ON (PROG)
SP1 Programming:
1.) Move the magnet to the desired SP1 position.
2.) Hold the programming switch in Position #1 until the
RUN
LED begins to flash (
≈
3 seconds)
Programming Mode is set up.
3.) Momentarily toggle the programming switch to Position #1 and release and repeat until
ZERO + SC
become lit.
4.) Hold the programming switch in Position #2 until
SC
begins to flash (
≈
3 seconds).
ZERO
is also lit.
5.) Enter the desired analog out at SP1 using the BCD switches (S1 = least significant bit, S5 = most significant bit).
6.) Hold the programming switch in Position #2 until
SC
is lit (
≈
3 seconds).
ZERO
is also lit.
7.) The output value at SP1 is now stored.
SP2 Programming:
1.) Move the magnet to the desired SP2 position
2.) Hold the programming switch in Position #1 until the
RE
LED begins to flash (
≈
3 seconds).
ZERO
is also
lit.
3.) Enter the desired analog out at SP2 using the BCD switches (S1 = least significant bit, S5 = most significant bit).
4.) Hold the programming switch in Position #2 until
SC
is lit (
≈
3 seconds).
ZERO will no longer be lit
.
5.) Hold the programming switch in Position #1 until the
RUN
LED is lit (
≈
3 seconds).
The output value at SP2 is now stored and the system has entered the Operations Mode.
NOTE:
Setting up a value outside the valid voltage range will
be detected and RE will flash rapidly to indicate an error.
NOTE:
Setting up a value outside the valid voltage range will
be detected and SC will flash rapidly to indicate an error.
IMPORTANT NOTES:
• SP1 and SP2 must be within the valid measuring range
• SP1 must be located nearer the sensor head than SP2
• SP1 and SP2 can have output values between -10 V
and +10 V
24