Step 2: Cable connection (Option 1: Disassembly of connection adapter)
2
Mount the cable gland at the connection adapter. Note the
instructions given by the manufacturer of the cable gland!
1
Loosen the five M4×10 screws (A/F 3). Remove the upper
lid. Loosen the six M4×40 screws (A/F 3) of the connection
adapter. Remove the connection adapter. See also Fig. 6.
5
Inspect surfaces and O-ring for damage. Wipe surfaces
clean and apply O-ring lube. Check the position of O-ring
between upper lid and connection adapter.
Tighten the screws of the upper lid crosswise with a
fastening torque of 1.2 Nm (see figure for right sequence).
1
2
3
4
5
3
Connect the cable to the sensor.
Note the connection wiring on page 19.
4
Inspect surfaces and O-ring for damage. Wipe surfaces
clean and apply O-ring lube. Tighten the screws of the
connection adapter with a fastening torque of 1.2 Nm.
The figures are examples.
Variations are possible, e.g. different cable colors
NOTICE
The example “Cable connection” is only valid for versions E and N of
the TH sensor. Refer to the corresponding installation requirements
and local regulations, if you like to connect a cable to the TH sensor
versions D and G.