DesCRIPtIoN

The 9468-ET 10/100Mbps Ethernet Isolator allows the interconnection of a Zone 2 or un-certified 
Safe Area device to the Intrinsically Safe 9400 series of Ethernet networking products, operating 
in the Hazardous Area.

The isolator provides a compact alternative solution to fibre optic cable and media converters and 
for when it is desirable to use Cat5e cables in preference to fibre.

The module requires a single supply from the Safe Area of 20…30Vdc at approx 220mA.

3.   INstALLAtIoN

WARNING:

 This equipment must be installed, operated and maintained only be trained competent 

personnel and in accordance with all appropriate international, national and local standard codes 
of practice and site regulation for intrinsically safe apparatus and in accordance with the instructions 
contained here. 

See also Sections 7, 8 & 9 for approvals and important conditions of safe use.

3.1  Protection

The module requires mounting within an enclosure providing a degree of protection of at least IP6x, 
in accordance with EN60529 and in a manner that does not impair the existing creepage and 
clearance distances. The enclosure must also comply with the requirements of Clauses 7 and 8 of 
EN50014 and be sealed to prevent the ingress of dust.

3.2  Mechanical mounting

3.2.1  DIN rail mounting

The module will ‘snap-fit’ onto standard DIN rail (TS35) to EN 50022. Height off rail - including any 
connectors but excluding cables = 106mm.

Tilt the module to engage the top DIN rail clips then rotate down and press to the DIN rail until the 
lower spring clip is properly engaged.

3.2.2  Flat panel mounting

The module has two fixing holes to enable it to be mounted with two M3.5 screws. Use the following 
dimension  diagram  to  establish  the  hole  positions.    Depth  -  including  connectors  but  excluding 
cables = 111mm.

Summary of Contents for 9468-ET

Page 1: ...Instruction Manual INM9468 9468 ET 10 100Mb Ethernet Isolator ...

Page 2: ...NSTALLATION 2 3 1 Protection 2 3 2 Mechanical mounting 2 3 4 Label marking 4 4 ENVIRONMENTAL 4 5 WASTE REMOVAL INFORMATION 4 6 ACCESSORIES 4 7 APPROVALS 5 8 FM CERTIFICATION INFORMATION 5 9 ATEX iecex CERTIFICATION INFORMATION 5 Measurement Technology Limited 2010 ...

Page 3: ...nk 10Mb or Link 100Mb Established Safe Area UTP Tx Rx Activity Hazardous Area UTP Link 10Mb or Link 100Mb Established Hazardous Area UTP Tx Rx Activity Transparent operation 10 100Mbps Full Half Duplex with Auto Negotiation Supports IEEE 802 3 10Base T 100Base TX DIN rail mounting module Note PoEx is a simple adaptation of the IEEE 802 3af Power over Ethernet PoE standard to bring the benefits to ...

Page 4: ...tructions contained here See also Sections 7 8 9 for approvals and important conditions of safe use 3 1 Protection The module requires mounting within an enclosure providing a degree of protection of at least IP6x in accordance with EN60529 and in a manner that does not impair the existing creepage and clearance distances The enclosure must also comply with the requirements of Clauses 7 and 8 of E...

Page 5: ...X 2 RX 3 TX 4 5 6 TX 7 8 HAZARDOUS AREA 10 100 BASE T Ethernet RJ45 TX RX crossed MDI X Connector marked blue Pin No Function 1 RX 2 RX 3 TX 4 Supply 12V PoEx 5 Supply 12V PoEx 6 TX 7 Supply 0V PoEx 8 Supply 0V PoEx When supply has been connected to screw terminals 14 15 When connecting the Cat5e cable to another device a straight connected RJ45 cable is used a crossover cable is not required as t...

Page 6: ...e Temperature 20 C 70 C Humidity 5 95 RH non condensing 5 WASTE REMOVAL INFORMATION The electronic equipment within must not be treated as general waste By ensuring that this product is disposed of correctly you will be helping to prevent potentially negative consequences for the environment and human health which could otherwise be caused by incorrect waste handling of this product For more detai...

Page 7: ...Ex nLc nAc ia IIC Ta 40 C to 70 C Cert no Sira 08ATEX4130X IECEx SIR 08 0032X for guidance on the Gc nLc nAc marking see specification for operating temperature range 8 FM CERTIFICATION INFORMATION Special Condition of Use Factory Mutual USA Canada 1 The Model 9468 ET shall be installed in compliance with the enclosure mounting spacing and segregation requirements of the ultimate application 9 ATE...

Page 8: ... the ic certified 9468 ET 10 100 Ethernet Isolator module does not satisfy Table 4 of EN 60079 0 2006 for equipment protection level Gc and could be a potential electrostatic charging hazard this must be taken into consideration during the installation of the modules b The nLc nAc certified 9468 ET 10 100 Ethernet Isolator module shall be installed in an ATEX Component Approved Ex e enclosure that...

Page 9: ...e Cc cable Co psu Ci app Lc cable Lo psu Li app L R cable Lo Ro psu 12VDC IS Power Supply 9469 WLAN AP Bridge PoEx Supply for Port 3 Device Supply for 9466 PoEx for 9461 via Port 3 Supply for 9466 PoEx for 9465 via Port 5 Supply for 9465 PoEx not used Supply for 9466 PoEx Supply for Port 5 Device Supply for 9469 PoEx Supply for Port 1 Device PoEx Supply for Port 3 Device No PoEx No PoEx PoEx for 9...

Page 10: ...ing of Typical Installation SIZE DWG NO REV A3 9400 System 4 SCALE SHEET 2 OF 2 CSL SCALE TITLE H G F E D C B A 8 7 6 5 4 3 2 1 H G F E D C B A 8 7 6 5 4 3 2 1 NOTE RJ45 ETHERNET PORTS ARE INTENDED FOR CONNECTION ONLY TO OTHER 9400 SERIES MODULES SHOWN ON THIS DRAWING With the exception of 9468 ET Safe Area port ...

Page 11: ...9 INM9468 2 May 2010 ...

Page 12: ...0092 Cinisello Balsamo MI Italy Tel 39 0 2 61802011 Fax 39 0 2 61294560 E mail info mtl inst it MTL Instruments KK MT Building 3F 2 7 5 Shiba Daimon Minato ku Tokyo Japan 105 0012 Tel 81 0 3 6430 3128 Fax 81 0 3 6430 3129 E mail sales mtlkk co jp Cooper Crouse Hinds Korea 12F Vision Tower 707 2 Yeoksam dong Gangnam gu Seoul 135 080 South Korea Tel 82 2 3484 6795 Fax 82 2 3484 6778 MTL Instruments ...

Reviews: