1
INM9468-2
May 2010
1.
FeAtURes
♦
Intrinsically Safe ATEX / IECEx certified
♦
FM / FMC approved
♦
Ga Ex ia IIC T4 GD (surface), Ma Ex ia I M1 (mining)
♦
Zone 2 / Safe Area mounting with Hazardous Area connections into Zone 1 and 0.
♦
Interfaces Zone 2 and non-approved devices to the Intrinsically Safe 9400 series.
♦
Total galvanic isolation (Um=253Vac) from Safe to Hazardous RJ45 ports
♦
Single Safe Area supply: 20…30V dc @ 220mA
♦
Extended temperature range (–20°C…+70°C)
♦
PoEx™ - “Power over Ethernet” power sourcing equipment - distributes device supplies via the RJ45 ports*
♦
10/100Mb Ethernet twisted pair (Cat5e) RJ45 Connections (100m max)
♦
Status LED’s for:
‘Power On’
Safe Area UTP ‘Link 10Mb’ or ‘Link 100Mb’ Established
Safe Area UTP ‘Tx/Rx Activity’
Hazardous Area UTP ‘Link 10Mb’ or ‘Link 100Mb’ Established
Hazardous Area UTP ‘Tx/Rx Activity’
♦
Transparent operation – 10/100Mbps, Full/Half Duplex with Auto-Negotiation
♦
Supports IEEE 802.3: 10Base-T, 100Base-TX
♦
DIN-rail mounting module
*Note – PoEx is a simple adaptation of the IEEE 802.3af Power over Ethernet (PoE) standard to
bring the benefits to the 9400 Range of Hazardous Area devices. This allows two spare pairs in the
existing Cat5e cable to distribute the power supply from a 9466-ETEthernet Switch (Power Sourcing
Equipment – PSE) to each of the devices connected to its five ports (PD – Powered Device). This
adaptation is necessary due to restrictions for Hazardous Area use. It is not implied that the device
conforms to the 802.3af (PoE) standard.
INM9468-2
May 2010
9468-et - ethernet Isolator