
INSTALLATION INSTRUCTIONS
!
WARNING
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY
RESULT IN A MALFUNCTION OR FAILURE OF THE
ALARM AND MAY VOID THE WARRANTY.
SHOCK HAZARD: Turn off power before installing.
Power Supply 12 VDC.
Recommended Wire Size 14 GA. TO 18 GA.
Connect the alarm to a properly fused circuit, maximum over
protection device rating 15 amps.
Connect to wiring or circuit that CANNOT be turned off by a
switch or ground fault protector. Only use UL or recognized
permanent wire connectors.
It is acceptable to connect the 62
Series CO alarm to the main disconnect. The alarm will be off along
with all other 12 volt equipment when the main disconnect is turned
to the off position. The RV must not be occupied when the main
disconnect is in the off position.
Follow these instructions carefully. Failure to follow these
instructions can damage the unit and void the warranty. Select a wall
location at least 4” off the floor.
62-541:
REFER TO “WHERE TO AND WHERE NOT TO
INSTALL”.
Install the back plate and drill a ¼” hole for the power
leads.
Connect the RED (+) power lead to the fused circuit. Connect
the BLACK lead to Ground (-). Slide the Detector enclosure onto
the mounting plate. Reconnect the power supply.
62-542:
REFER TO SECTIONS "WHERE TO INSTALL" AND
"WHERE NOT TO INSTALL". This alarm requires a 1” clearance
to recess the case. Cut a 3.5” W x 2.75” H hole. Connect the RED
(+) power lead to the fused circuit. Connect the BLACK lead to
Ground (-). Fasten the unit to the wall using the two screw holes
located on the ends of the case. Reconnect the power supply.
NOTE: All connections must be in accordance with the National
Electrical Code in the Unites Stated and the Canadian Electric
Code in Canada.
TEST PROCEDURE
!
WARNING
TO REDUCE THE RISK OF CARBON MONOXIDE POISONING,
TEST THIS ALARM’S OPERATION AFTER THE RV HAS BEEN
IN STORAGE, BEFORE EACH TRIP AND AT LEAST ONCE PER
WEEK DURING USE
.
!
WARNING
WARNING: THE TEST BUTTON ONLY TESTS THE
ALARM CIRCUIT NOT THE SENSORS. TO TEST THE CO
SENSOR USE A CAN OF SAFE-T-ALERT CO TEST GAS TO
TEST THE 400 PPM CALABRATION POINT. DO NOT TRY
TO GENERATE CO TO TEST THE ALARM.
The TEST/RESET
button tests all ELECTRICAL functions of the alarm. It does not
check the sensor operation.
The alarm may be tested at any time -The TEST/Mute switch is
located on the front of the alarm Press and hold the test button for 1
second. The alarm is working properly if the GREEN indicator light
changes color to RED and the horn beeps 4 times.
IMPORTANT
-
If this alarm does not test properly return it immediately
for repair or replacement.
OPERATION
Each time the unit is first powered up, the CO sensor requires a ten (10)
minute initial warm-up period to clean the sensor element and achieve
stabilization. The GREEN LED indicator will flash on and off during the 10
minute warm-up period. This unit cannot go into a CO alarm during the
warm-up period. To test your unit during the warm-up period, press the test
button. See Test Procedure in this manual. After the warm-up period, the
GREEN power ON indicator should glow continuously
If the ON indicator
light does not light, see the section,
Trouble-Shooting Guide
, in this
manual for further information.
Do not attempt to fix it yourself.
Brownout Protection -
The unit can tolerate short power interruptions and
brownouts where the circuit voltage drops as low as 1VDC. If the brownout
lasts too long, the unit will reset and operate as described above.
LOW POWER OPERATION: This alarm will operate normally
down to7 VDC. Do not operate this alarm below 7 VDC.
VISUAL AND AUDIBLE ALARM SIGNALS
This SAFE-T-ALERT
TM
CO Alarm is designed to be easy-to-operate. The
alarm has an indicator light that displays a specific color for each monitored
condition. There also is a matching sound pattern for alarm conditions.
CO ALARM
The Red CO LED will flash and the alarm will sound 4 “BEEPS” then
silent for 5 Seconds
.
These signals
indicate that the CO level is over 35
ppm.
IMMEDIATE ACTION IS REQUIRED.
See
Procedures To Take
During An Alarm
. This cycle will continue until the TEST/Mute button on
the front of alarm is pressed. Ventilate the RV. The RED light will stay ON
until the CO has cleared, or the alarm will reactivate in approximately 6
minutes if the CO is still present. DO NOT RE-ENTER THE RV. This
alarm will return to normal operation after the RV is properly ventilated.
MALFUNCTION/SERVICE SIGNAL
If any malfunction is detected, the
Operational/CO LED will alternate Red/Green and the alarm will sound
once every 15 seconds. Press the Test/Mute button. If the Test/Mute button
does not clear the signals, check the battery voltage.
If the battery voltage
is not low and the unit will not return to normal operation,
immediately
remove the alarm and return for service or warranty replacement.
See
the warranty section in this manual.
OPERATION
NORMAL
CO ALARM
ALARM
MALFUNCTION
END OF LIFE
WARM UP CYCLE
(ABOUT 10 MINUTES)
AUDIBLE SIGNAL VISUAL SIGNAL
NONE STEADY GREEN
4 “BEEPS” STEADY RED
5 SECONDS OFF
5
“
“ BEEP EVERY ALTERNATING
30 SECONDS RED/GREEN
B BEEPS EVERY RED RED GREEN GREEN
25-30 SECONDS FLASHING
NO SOUND FLASHING GREEN