General Safety Instructions

 

 

WARNING 

High Voltage! Only a qualified electrician can carry out the electrical 
installation of this filter. 

High voltage is used in the operation of this filter. Use Extreme caution to 
avoid contact with high voltage when operating, installing or repairing this 
filter.

 Injury or death may result if safety precautions are not 

observed.  

 

WARNING

 

The opening of the branch circuit protective device may be an indication 
that a fault current has been interrupted. To reduce the risk of fire or 
electrical shock, current-carrying parts and other components of the filter 
should be examined and replaced if damaged. 

An upstream disconnect/protection device must be used as required by 
the National Electrical Code (NEC) or governing authority. 

Even if the upstream disconnect/protection device is open, the drive down 
stream of the filter may feedback high voltage to the filter. The drive 
safety instructions must be followed. 

Injury or death may result if safety 

precautions are not observed.

 

The filter must be grounded with a grounding conductor connected to all 
grounding terminals. 

Only spare parts obtained from MTE Corporation or an authorized MTE 
distributor can be used. 

After removing power, allow at least five minutes to elapse and verify that 
the capacitors have discharged to a safe level before contacting internal 
components. Connect a DC voltmeter across the capacitor terminals and 
ensure that the voltage is at a safe level. 

 

Caution 

Loose or improperly secured connections may damage or degrade filter 
performance. Visually inspect and secure all electrical connections before 
power is applied to the filter. 

Product should not be mounted on wood or any other combustible 
surface.  Doing so could lead to fire or damage to the product. 

The user of this filter must assure that the input voltage and frequency is 
correct for the filter rating and that the voltage applied falls within the 
rated operating tolerance envelop specified for the filter. For sever power 
line applications where the power feed is likely to experience surges and 
transients that exceed the input voltage rating, it is recommended that a 
TVSS (Transient Voltage Surge Suppression) or SPD (Surge Protection 
Device) be deployed ahead of the filter to reduce the possibility of 
exceeding the filter rated voltage. Consult with TVSS or SPD 
manufacturer to determine the correct protection for your power line 
conditions. 

Filter must be mounted in the proper orientation per labeling. 

Fans must be operating properly before powering up the filter. 

 

 

Summary of Contents for Matrix APAX

Page 1: ...FORM MX IG E REL January 2018 REV 002 2018 MTE Corporation WARNING High Voltage Only a qualified electrician can carry out the electrical installation of this filter Quick Reference How to Install Pa...

Page 2: ...This page intentionally left blank...

Page 3: ...GROUNDING 8 POWER WIRING CONNECTION 9 BASIC SCHEMATIC DIAGRAMS 10 INTERCONNECTION DIAGRAM 11 CONTACTOR WIRING OPTION 12 4 START UP 13 STARTUP CHECKLIST 13 5 TROUBLESHOOTING 14 HARMONIC FILTER FIELD C...

Page 4: ...Voltage Warning warns of situations that dangerously high voltage is involved Failure to use proper precautions may lead to serious injury or even death WARNING General Warning warns of situations tha...

Page 5: ...ed from MTE Corporation or an authorized MTE distributor can be used After removing power allow at least five minutes to elapse and verify that the capacitors have discharged to a safe level before co...

Page 6: ...er The Matrix APAX Harmonic Filter has been subjected to demanding factory tests before shipment Carefully inspect the shipping container for damage that may have occurred in transit Then unpack the f...

Page 7: ...environment Avoid locations where the filter would be subjected to excessive vibrations It is recommended that the panel is mounted vertically with the fan at the bottom to allow airflow upwards and...

Page 8: ...should be used in conjunction with thermal switch to turn off the drive to prevent filter damage due to abnormal operating conditions The temperature switch is normally closed and will open when an i...

Page 9: ...ors with a minimum temperature rating of 75 degrees C Wiring Checks Using Figure 3 1 p10 visually check the wired components to confirm verify and correct wiring Then with a multi meter check phase to...

Page 10: ...Matrix APAX Installation Guide 380V 415V Form MX IG E January 2018 REV 002 mtecorp com 10 Basic Schematic Diagrams Figure 3 1 Basic Schematic Diagram...

Page 11: ...Matrix APAX Installation Guide 380V 415V 11 mtecorp com Form MX IG E January 2018 REV 002 Interconnection Diagram Figure 3 2 Matrix APAX Panel Mounted Interconnection...

Page 12: ...r to add disconnect options to meet their applications Figure 3 3 p12 shows a representation of the contactor wiring block the terminal block varies depending on model size Refer to Figure 3 2 p11 for...

Page 13: ...the utility drive and motor is in accordance with the power wiring connection diagrams shown in installation instructions section 3 Check that moisture has not condensed on the filter components If mo...

Page 14: ...UTIONS ARE NOT OBSERVED To aid in troubleshooting an interconnection diagram and a troubleshooting guide that lists potential problems and solutions are included Figure 3 2 Matrix APAX Panel Mounted I...

Page 15: ...7 Using a multi meter set to read 100K ohms check a Phase to phase U1 V1 W1 U1 mechanically activate contactor if present after reactor and caps charge reading should be about 40K total equivalent bre...

Page 16: ...Filter output voltage is not within specification Possible cause Filter input voltage is not within specification Solution Check the AC input line voltage and verify that it is within tolerance Refer...