MTE dV Sentry Installation Manual Download Page 7

dV Sentry

TM

 Installation Guide 208V 

 600V

 

7                                          mtecorp.com                   Form: DVS-IG-E January 2018 REV. 003 

Grounding 

 

NOTE: For cable shield grounding follow the drive manufacturer’s recommendations. 

 

Location & Spacing 
 

Panel mounted (open-panel) filters are 

designed for mounting in the customer’s enclosure. 

Include the power dissipation of the filter along with all the other components located in the 
panel to determine the internal temperature rise and cooling requirements of the enclosure. A 
general guideline is to allow a side clearance of four (4) inches and a vertical clearance of six 
(6) inches for proper heat dissipation and access within the enclosure. Clearances may be less 
if proper ventilation exists.  Filter components must operate within temperatures specified in this 
manual or filter operating life will be compromised.  Also be aware of minimum electrical 
clearances as defined by the appropriate system safety standard(s). Panel mounted dV Sentry 
Filters generate heat and should be positioned away from heat sensitive components. Ensure 
that proper panel orientation is maintained. Avoid locations where the filter would be subjected 
to excessive vibrations. Locate the filter as close to the drive as possible. For applications where 
the cable length exceeds fifty (50) feet between the drive and filter, contact MTE. 
 
General purpose NEMA 1/2 and NEMA 3R enclosed filters are designed for floor mounting in an 
environment suitable for the enclosure type. Do not install in or near a corrosive environment. 
Avoid locations where the filter would be subjected to excessive vibrations. Allow a minimum 
side and back clearance of eight (8) inches and front clearance of thirty-six (36) inches for 
proper heat dissipation and access. Locate the filter as close to the drive as possible. 
 

 

 

 

WARNING

 

The filter must always be grounded with a grounding conductor connected 
to ground terminals. 

For panel mounted 

units, ensure a 2” x 2” area is cleaned of paint and 

varnish on lower mounting bracket for ground connection. 

Summary of Contents for dV Sentry

Page 1: ...RM DVS IG E REL January 2018 REV 003 2018 MTE Corporation WARNING High Voltage Only a qualified electrician can carry out the electrical installation of this filter Quick Reference How to Install Page...

Page 2: ...NDING 7 POWER WIRING CONNECTION 9 BASIC SCHEMATIC DIAGRAMS 10 INTERCONNECTION DIAGRAM PANEL 3A 110A AND ENCLOSED 3A 600A 11 INTERCONNECTION DIAGRAM MODULAR 130A 600A 12 TORQUE RATINGS 13 4 START UP 14...

Page 3: ...NING High Voltage Warning warns of situations that dangerously high voltage is involved Failure to use proper precautions may lead to serious injury or even death WARNING General Warning warns of situ...

Page 4: ...cal Code NEC or governing authority Even if the upstream disconnect protection device is open the drive down stream of the filter may feedback high voltage to the filter The drive safety instructions...

Page 5: ...Protection Filter has been subjected to demanding factory tests before shipment Carefully inspect the shipping container for damage that may have occurred in transit Then unpack the filter and carefu...

Page 6: ...ith a modular reactor Floor mounted general purpose NEMA 1 2 3R cabinets 3A 600A Reactor and resistor resistor panel are supplied in a cabinet with all items pre wired together NOTE 3A 110A panel moun...

Page 7: ...tem safety standard s Panel mounted dV Sentry Filters generate heat and should be positioned away from heat sensitive components Ensure that proper panel orientation is maintained Avoid locations wher...

Page 8: ...eactor temperature of 150 C is reached See Table 4 1 below for contact rating information and the drive user manual for interconnection information Table 4 1 Over Temperature Switch NC Switch opens at...

Page 9: ...4 2 p11 For all filters supplied in general purpose NEMA 1 2 3R cabinets interconnection between the filter its power source and the drive is shown in Figure 4 3 p12 Wire gauge range and terminal tor...

Page 10: ...dV SentryTM Installation Guide 208V 600V Form DVS IG E January 2018 REV 003 mtecorp com 10 Basic Schematic Diagrams Figure 4 1 Basic Schematic Diagram...

Page 11: ...dV SentryTM Installation Guide 208V 600V 11 mtecorp com Form DVS IG E January 2018 REV 003 Interconnection Diagram Panel 3A 110A and Enclosed 3A 600A Figure 4 2 Panel Mounted and Enclosed Diagram...

Page 12: ...dV SentryTM Installation Guide 208V 600V Form DVS IG E January 2018 REV 003 mtecorp com 12 Interconnection Diagram Modular 130A 600A Figure 4 3 Open Panel Diagram...

Page 13: ...A 55 6 16 N A N A N A 65 6 N A N A N A N A 80 4 N A N A N A N A 110 2 N A N A N A N A 130 1 N A RESPANEL 012 14 16 160 4 2x or 2 0 N A RESPANEL 012 14 16 200 3 2x or 3 0 N A RESPANEL 012 14 16 250 1 2...

Page 14: ...sure that All filter ground terminals are connected to ground Power wiring to the utility drive filter and motor is in accordance with the power wiring connection diagrams shown in installation instru...

Page 15: ...rams and a troubleshooting guide that lists potential problems and solutions are included Figure 4 2 Panel Mounted and Enclosed Diagram p11 Figure 4 3 Open Panel Diagram p12 Table 6 2 Troubleshooting...

Page 16: ...nt voltage and shutdown parameters are valid PROBLEM dV Sentry filter runs Hot Possible cause Normal operation reactor 150 C and resistors 300 C Solution Caution Parts are very hot and may cause burns...

Reviews: