MTE dV Sentry Installation Manual Download Page 3

dV Sentry

TM

 Installation Guide 208V 

 600V

 

3                                          mtecorp.com                   Form: DVS-IG-E January 2018 REV. 003 

1. WARNINGS 

Warnings and Cautions 

There are two types of warnings in this manual: 

 
The following symbols are used in this manual: 

 

Product Safety Labeling 

The following labels are placed on the dV Sentry product:

 

 

 

 

WARNING

 

WARNING describes situations that can lead to serious faults, 
physical injuries, or even death. 

 

Caution

 

Caution describes situations that can lead to malfunction or 
possible equipment damage. 

 

WARNING

 

High Voltage Warning: warns of situations that dangerously 
high voltage is involved. Failure to use proper precautions may 
lead to serious injury or even death. 

 

WARNING

 

General Warning: warns of situations that can result in serious 
injury or death if proper precautions are not used. 

 

Caution

 

General Caution: identifies situations that could lead to 
malfunction or possible equipment damage. 

 

Label notes to installer to refer to instruction manual first before 
installing.

 

 

High Voltage: surfaces on product can have high voltage which can 
cause injury. 

 

 

Connect Thermal Switch: connecting the thermal switch can reduce 
risk of damage. 

 

Hot Surfaces: surfaces of product can be hot at times and cause 
burns. 

Summary of Contents for dV Sentry

Page 1: ...RM DVS IG E REL January 2018 REV 003 2018 MTE Corporation WARNING High Voltage Only a qualified electrician can carry out the electrical installation of this filter Quick Reference How to Install Page...

Page 2: ...NDING 7 POWER WIRING CONNECTION 9 BASIC SCHEMATIC DIAGRAMS 10 INTERCONNECTION DIAGRAM PANEL 3A 110A AND ENCLOSED 3A 600A 11 INTERCONNECTION DIAGRAM MODULAR 130A 600A 12 TORQUE RATINGS 13 4 START UP 14...

Page 3: ...NING High Voltage Warning warns of situations that dangerously high voltage is involved Failure to use proper precautions may lead to serious injury or even death WARNING General Warning warns of situ...

Page 4: ...cal Code NEC or governing authority Even if the upstream disconnect protection device is open the drive down stream of the filter may feedback high voltage to the filter The drive safety instructions...

Page 5: ...Protection Filter has been subjected to demanding factory tests before shipment Carefully inspect the shipping container for damage that may have occurred in transit Then unpack the filter and carefu...

Page 6: ...ith a modular reactor Floor mounted general purpose NEMA 1 2 3R cabinets 3A 600A Reactor and resistor resistor panel are supplied in a cabinet with all items pre wired together NOTE 3A 110A panel moun...

Page 7: ...tem safety standard s Panel mounted dV Sentry Filters generate heat and should be positioned away from heat sensitive components Ensure that proper panel orientation is maintained Avoid locations wher...

Page 8: ...eactor temperature of 150 C is reached See Table 4 1 below for contact rating information and the drive user manual for interconnection information Table 4 1 Over Temperature Switch NC Switch opens at...

Page 9: ...4 2 p11 For all filters supplied in general purpose NEMA 1 2 3R cabinets interconnection between the filter its power source and the drive is shown in Figure 4 3 p12 Wire gauge range and terminal tor...

Page 10: ...dV SentryTM Installation Guide 208V 600V Form DVS IG E January 2018 REV 003 mtecorp com 10 Basic Schematic Diagrams Figure 4 1 Basic Schematic Diagram...

Page 11: ...dV SentryTM Installation Guide 208V 600V 11 mtecorp com Form DVS IG E January 2018 REV 003 Interconnection Diagram Panel 3A 110A and Enclosed 3A 600A Figure 4 2 Panel Mounted and Enclosed Diagram...

Page 12: ...dV SentryTM Installation Guide 208V 600V Form DVS IG E January 2018 REV 003 mtecorp com 12 Interconnection Diagram Modular 130A 600A Figure 4 3 Open Panel Diagram...

Page 13: ...A 55 6 16 N A N A N A 65 6 N A N A N A N A 80 4 N A N A N A N A 110 2 N A N A N A N A 130 1 N A RESPANEL 012 14 16 160 4 2x or 2 0 N A RESPANEL 012 14 16 200 3 2x or 3 0 N A RESPANEL 012 14 16 250 1 2...

Page 14: ...sure that All filter ground terminals are connected to ground Power wiring to the utility drive filter and motor is in accordance with the power wiring connection diagrams shown in installation instru...

Page 15: ...rams and a troubleshooting guide that lists potential problems and solutions are included Figure 4 2 Panel Mounted and Enclosed Diagram p11 Figure 4 3 Open Panel Diagram p12 Table 6 2 Troubleshooting...

Page 16: ...nt voltage and shutdown parameters are valid PROBLEM dV Sentry filter runs Hot Possible cause Normal operation reactor 150 C and resistors 300 C Solution Caution Parts are very hot and may cause burns...