MAINTENANCE AND OPERATING MANUAL
Technical parameters for heat pump space heaters and heat pump combination heaters
HAS T 070÷140
7
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice.
Reproduction of this manual is strictly prohibited.
1 . 5
P e r f o r m a n c e d a t a
The performance of the unit depends mainly on the flow rate and the temperature of chilled water (CHILLER) or heated
water (HEAT PUMP) and on the ambient temperature.
Performance values are defined at the time of the contract, refer to the offer data if necessary.
1 . 6
N o i s e
Data concerning noise levels are shown in the appendix to the manual.
1 . 7
H o w t o i n t e r p r e t t h e a l p h a n u m e r i c s t r i n g
ATTENTION
See the table concerning the alphanumeric string in the appendix.
The alphanumeric string is shown on the metal data plate on the cover page of this manual.
T
E C H N I C A L
P A R A M E T E R S
F O R
H E A T
P U M P
S P A C E
H E A T E R S
A N D
H E A T
P U M P
C O M B I N A T I O N
H E A T E R S
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps.
For low temperature heat pumps, parameters shall be declared for low-temperature application.
Parameters shall be declared for average climate conditions.
This symbol shown alongside appears in some refrigerant circuit diagrams and electrical
diagrams. This symbol refers to the alphanumeric string reported in the manual. The upper
box (X) identifies the position of the string, the lower box (Y) identifies the assigned value.
The empty alphanumerical string is circled in the adjacent figure; each
position in the upper row is associated with an alphanumeric value in the
lower row (0, 1, 2, A, B, etc.) and each character is associated with a
specific feature of the unit.
Model/Version
HAST 070 N
Air-to-water heat pump:
YES
Water-to-water heat pump:
NO
Brine-to-water heat pump:
NO
Low-temperature heat pump:
YES
Equipped with a supplementary heater:
NO
Heat pump combination heater:
NO
Item
Symbol
Value
Unit
Item
Symbol
Value
Unit
Rated heat output
Prated
163,15
kW
Seasonal space heating energy
efficiency
η
s 117,69
%
Seasonal coefficient of performance
SCOP
3,02
--
T
j
= – 7 °C
Pdh
124,75
kW
Tj = – 7 °C
COPd
or PERd
2,48
-- o %
T
j
= + 2 °C
Pdh
160,48
kW
Tj = + 2 °C
COPd
or PERd
3,43
-- o %
T
j
= + 7 °C
Pdh
184,53
kW
Tj = + 7 °C
COPd
or PERd
4,14
-- o %