COMMISSIONING 

For sensors that e.g. can be poisoned by silicones like all semiconductor and catalytic bead sensors, it is imperative to 
remove the protective cap supplied only after all silicones are dry, and then energize the device. 

The  protective  cap  has  to  be  used  in  subsequent  cleaning  work  with  water  jet  or  steam,  too,  in  order  to  protect  the 
sensor. 

For fast and comfortable commissioning we recommend proceeding as follows. For digital devices with self-monitoring 
all internal errors are visible via the LED. All other error sources often have their origins in the field, because it is here 
where most of the causes for problems in the field bus communication appear. 

 

Optical Check 

 

Right cable type used. 

 

Correct mounting height according to definition in Mounting. 

 

Led status 

 

Protective cap removed from the sensor. 

 

Run-in period 

In order to obtain an optimum fresh air setting, it is necessary to run the unit continuously at least for 48 hours without 
shutdown under unpolluted ambient air conditions. 

 

Selection Gas Type with Unit 

The selection of the desired and connected gas sensor type is made by pre-set values. 

If other gas sensor types are connected, you have to adjust them with the configuration tool, because otherwise the 
device will respond with an error message.  

Connection possible as digital sensor cartridge SC2. 

The selection contains all necessary information for the controller and is also used for comparing the real, digital data 
with the settings. 

This feature increases the user and operating security.  

There is an entry available per gas type for each unit; at the moment there are 100 selection options. 

Summary of Contents for PolyGard 2 MSC2

Page 1: ...bH W rdinger Str 27 27A 94060 Pocking Germany Specifications subject to change without notice PolyGard is a registered trademark of MSR Electronic GmbH PolyGard 2 MSC2 Multi Sensor Controller Datashee...

Page 2: ...5 interface with serial protocol For convenient operation the MSC2 is already completely configured and parameterized ex works The intended sites within the ambient conditions as specified in the Tech...

Page 3: ...Buzzer status LED red yellow green ALARM RELAYS 3 3x Alarm relays POWER SUPPLY 5 90 240 V AC 24 V DC 5 VA 7 90 240 V AC 24 V DC 15 VA HOUSING C Housing type C 130 x 130 x 75 mm ELECTRICAL CONNECTION...

Page 4: ...W Note Relay 1 2 Status OFF means Alarm off Relay coil energized Status ON means Alarm on Relay coil de energized Note Relay 3 Status OFF means No fault and MSC2 in normal operation Relay coil energiz...

Page 5: ...n flashing represents a connection option for warning devices to improve visibility If flashing is set this must not be used as a safe output circuit any more A combination of relay mode energized wit...

Page 6: ...from above the sensor head SC downwards Observe possible constructor s instructions Mounting Controller Wiring The technical requirements and regulations for wiring electrical security fire protection...

Page 7: ...in the field because it is here where most of the causes for problems in the field bus communication appear Optical Check Right cable type used Correct mounting height according to definition in Moun...

Page 8: ...100 Vol 2066 R11 R11 ppm 2059 R12 R12 20 2000 ppm 2070 R22 R22 20 300 ppm 2061 R23 R23 20 2000 ppm 2060 R32 R32 ppm 2064 R123 R123 20 300 ppm 2077 R134a R134a 20 300 ppm 2063 R1234yf R1234yf ppm 2065...

Page 9: ...erial No Date of Production Mainten interval Mainten Password AV Overlay AV Time Power On Time Error Time CFM dupl Note Note down 1900 V time ppm 0 0 0 90 30 30 Analog Output 1 Outp source Oper Signal...

Page 10: ...1 A2 A3 A4 A1 A2 A3 A4 01 active n CO2 Vol 5 0 5 1 1 1 0 2 0 0 CV 0 0 0 0 1 R1 R2 R3 R4 02 inactive n 03 inactive n Change of values after replugging the jumper closed 01 active n CO2 Vol 5 1 1 8 1 1...

Page 11: ...utton on the horn the horn acknowledgment must be checked After removal of the reference gas all outputs must automatically return to its initial position Other than the simple functional testing it i...

Page 12: ...y third parties every customer receives his own internal project key All projects of the customer are delivered with this key The key is also stored in each MSC 06 STL Tool that the respective custome...

Page 13: ...WH BL24 Tast SPECIFICATIONS SENSOR CARTRIDGE Sensor element Gas type Carbon dioxide CO2 Sensor element Infrared NDIR Measuring range 5 vol Measuring interval 2 sec Accuracy 10 of range Response time t...

Page 14: ...rol installations and the latest edition of the National Electrical Code ANSI NFPA70 The equipotential bonding required also e g secondary potential to earth or grounding measures must be carried out...

Page 15: ...MSR Electronic GmbH W rdinger Str 27 27A 94060 Pocking Germany Specifications subject to change without notice PolyGard is a registered trademark of MSR Electronic GmbH...

Reviews: