MSA ZGARD C Instruction Manual Download Page 7

 

 

Section 3 

ZGARD C 1-Channel Controller 

General Information 

 

OPERATING SPECIFICATIONS

 

Remote Sensor Input

 

 

1 only, 4-20mA analogue, 2 or 3wire 

OR

 RS485 digital data bus, 4-wire connection

 

Remote Sensor Power

   

24Vdc at 100mA / Input

 

Network Capacity 

1 Remote Gas Sensor 

Power Requirements 
(Optional)

 

 

 

Standard 110Vac, 50/60 Hz ± 10% at 0.15 Amps 
220Vac, 50/60 Hz ± 10% at 0.10 Amps; 24Vdc 

±

 10% at 0.5 Amps 

Temperature

 

 

 

Operating: -10° to 40°C (14° to 104°F); Storage: -20° to 50°C (-4° to 122°F) 

LED Readout

 

1 + 3 Digit LED display exhibits the channel number and gas level, at 2 second intervals

 

Status LED Indicators

 

 

Power, Warning, Alarm and Sensor OK

 

Audible Alarm   

Electronic device, 93 dB @ 0.3 meters with variable sound selection

 

Pushbutton 

Alarm reset and Silence function

 

Alarm & Warning Set points

 

Factory set at 35% and 50% Full-Scale, unless otherwise specified (Field Adjustable)

 

Sensor Fail Set point

 

 

Non-adjustable

 

Time Delays 

Fixed 5 minutes ON delay for Alarm and 5 minutes OFF delay for Warning 

or 

manually 

adjusted from 0 to10 minutes

 

Relay Outputs 

Warning Relay, Alarm Relay and Sensor Fail Relay: Form C - SPDT 

Relay Action 

Alarm Relay Latching or Non-Latching, jumper selected 

Relay Contacts Rating

   

10 Amps 1/8 H.P., 125Vac, 5 Amps, 30Vdc, 6 Amps 1/8 H.P., 277Vac 

(Optional) Signal Output 

4-20mA analogue output 

Enclosure 
(Optional) 

Metal NEMA 1 
Fiberglass NEMA 4X design 

Dimensions

 

 

 

11.5” H (292 mm) x 10” W (254 mm) x 3.75” D (95 mm) 

Weight

   

 

4.5kg (10 lbs.) 

Certification  

 

ENTELA (to CSA Standards) 

 

Sensor Input: 

The ZGARD C 1-Channel controller 

accepts 1 remote gas sensor. The MSA ZGARD S or 
GS, 4-20mA 2 or 3-wire analogue or RS485 type 
sensor. The RS485 serial communication sensors are 
automatically recognized by the controller and establish 
the sensor range and gas code type. 
 

Readout: 

LED display exhibits the corresponding sensor 

gas concentration level.  
 

Warning and Alarm Set Points: 

The Warning and Alarm 

threshold levels are independently adjustable on the 
controller and can be set to any value between 0 and 
100% Full-Scale (FS).  
 

Delay Function: 

There are two user jumper selected 

methods for setting the ZGARD C 1-Channel controller 
warning and alarm delays. The first uses pre-
programmed, fixed delays of 5 minutes OFF delay for 
warning and 5 minutes ON delay for alarm. The second 
allows adjusting of the delays from 0 to 10 minutes using 
potentiometers.  
 

Warning and Alarm Scheme: 

During a Warning event, 

the Warning (Amber) LED will turn on and the warning 
relay will be activated. No audible alarm is set off at this 
time. Once a warning occurrence has been abated, the 
associated warning LED will turn off and the warning 
relay will be deactivated. If the 5 minute delay feature is 
selected, then this action takes place after a 5 minute 

delay period.  During an Alarm event, the associated 
Alarm (Red) LED will turn on and the alarm relay will be 
activated. If the 5 minute delay feature is selected and the 
alarm event has prolonged for a period of 5 minutes, then 
the alarm relay will be activated and the audible device 
will sound. Pressing the reset button on the front panel 
will silence the audible device. Once the alarm 
occurrence has been abated, the audible device will 
silence (if not silenced already by reset button) and the 
alarm relay will be deactivated. If any other active 
channels reach the alarm state, the audible device will 
sound with every new alarm event. Once all of the active 
channels have been cleared of alarm events, the audible 
device will silence (if not silenced already by reset button) 
and the alarm relay will be deactivated. 
 

Sensor Fail: 

If an analog sensor is used and the input is 

between 1mA and 3.5mA, the Sensor OK LED will turn 
off and the Sensor Fail Relay will be activated. Any 
analog input below 1.0mA causes the controller to ignore 
that analog input and treat that sensor as an RS485 type 
sensor. If there is a lose of communication between the 
controller and the remote gas sensor residing on the 
RS485 network, the Sensor Fail Relay will be activated 
and the Sensor OK LED will turn off. 
 

Optional 4-20mA Output: 

The analogue output 

continuously represents the signal generated by the 
remote sensor output. 

 

 

 
 
 
 

3.0

Summary of Contents for ZGARD C

Page 1: ...warranties made by Mine Safety Appliances Company with respect to these Products are voided if the products are not installed used and serviced in accordance with the instructions in this user guide...

Page 2: ...ufacturers of such components THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AND IS STRICTLY LIMITED TO THE TERMS HEREOF SELLER SPECIFICALLY DISCLAIMS ANY WARRANTY OF...

Page 3: ...luded as part of the installation and as a routine inspection of the system 5 Use only genuine MSA replacement parts when performing any maintenance procedures provided in this manual Failure to do so...

Page 4: ...g Specifications and Features 4 0 Installation and Set up Display Mode Number of Remote Sensor Inputs 4 1 Relay Function Setting up the Warning and Alarm Delays 4 2 Audible Alarm Device Setting Warnin...

Page 5: ...ZGARD C Controllers This is a quick guide for determining the functionally capability and configuration of each controller ZGARD C CONTROLLER MODEL 1 CHANNEL 4 CHANNEL Number of Remote Sensors 1 4 Po...

Page 6: ...controller according to the required application Also refer to the ZGARD C controllers Installation Outline drawings located in the back of this manual which provides important information regarding...

Page 7: ...lue between 0 and 100 Full Scale FS Delay Function There are two user jumper selected methods for setting the ZGARD C 1 Channel controller warning and alarm delays The first uses pre programmed fixed...

Page 8: ...ct the actual operating range of the incumbent remote gas sensors There are two display mode options A and B and is selected by placing Jumper H2 in the required position If jumper H1 4 is OUT Range A...

Page 9: ...allows adjusting of the delays from 0 to 10 minutes via two potentiometers labeled Warning Delay Alarm Delay To select the adjustable delay jumper H1 5 is NOT inserted Removing the jumper activates t...

Page 10: ...button will silence the audible alarm but will not have any effect on the alarm LED on the front panel or the alarm relay Warning and Alarm Set Points There are two methods for setting the warning an...

Page 11: ...SPAN potentiometer can be used to perform these To adjust the output to 4 20mA for 0 100 input factory setting when using a 4 20mA type sensor apply a 0 4mA signal to the input and adjust the ZERO pot...

Page 12: ...adjustable on the controller and can be set to any value between 0 and 100 Full Scale FS Delay Function There are two user jumper selected methods for setting the ZGARD C 4 Channel controller warning...

Page 13: ...a special Display Range that displays the first two channels 1 2 as 0 10 0ppm and the second two channels 3 4 as 0 100ppm This is useful for Carbon Monoxide CO Nitrogen Dioxide NO2 applications Remote...

Page 14: ...of the delays from 0 to 10 minutes via two potentiometers labeled Warning Delay Alarm Delay To select the adjustable delay jumper H1 5 is NOT inserted Removing the jumper activates the associated pot...

Page 15: ...nce the audible alarm but will not have any effect on the alarm LED on the front panel or the alarm relay Warning and Alarm Set Points There are two methods for setting the warning and alarm set point...

Page 16: ...can be used to perform these To adjust the output to 4 20mA for 0 100 input factory setting when using a 4 20mA type sensor apply a 0 4mA signal to one of the input and adjust the ZERO potentiometer...

Page 17: ...RESET button to silence 7 Allow the associated remote gas sensors to stabilize Refer to the appropriate gas sensor manual for further details Depending on the controller s warning alarm and delay sett...

Page 18: ...nuine MSA replacement parts when performing any maintenance on the ZGARD C Controllers Failure to do so may seriously impair instrument performance Repair or alteration of the ZGARD C controllers beyo...