Configuring the Gateway
EZ Gateway Start-up Guide
22
6.2.2 Modbus TCP/IP and Modbus RTU
Parameter
Definition
All Connections
Framing Timeout
Sets time EZ Gateway will wait for a message frame to complete on the network.
This is useful on busy Modbus networks where unknown messages for other
devices may cause longer timeouts. Legal values are 0
- 2147483647
milliseconds (0 means disabled).
Accept Broadcast
Select whether server will accept broadcast messages.
Modbus TCP/IP Settings
IP Port
The default is 502, but other port numbers can be specified.
Max Sessions
The maximum sessions that will be accepted by the server side.
Inactivity Timeout
The FieldServer will close the connection opened by the client if there is no
activity for this time period.
Multiple Server Messages
Enable or disable the ability to parse multiple messages in a stream.
Modbus RTU Settings
Parity, Data Bits, Stop Bits,
and Baud Rate
Specify desired values.
Figure 22: Connection Parameters
Figure 21: Connection Settings