Remote Alarm units
AU-106, AU-206
15
Table 8 – Check list № 3. Insulation resistance check of power circuits
To be done
Routine
Man-hours per
1 Product
Insulation resistance
check of power cir-
cuits
Using ohmmeter check insulation resistance between
conductors and the Product’s casing. Insulation re-
sistance shall not exceed 1 Mohm
1 person
15 mins
Table 9 – Check list № 4. Test of output voltage conformance
To be done
Routine
Man-hours per
1 Product
Test of output volt-
age conformance
Connect voltmeter to output contacts. Measure voltage
on the output terminals. Voltage value shall not exceed
the value represented in Table 1
1 person
15 mins
3.4
P
RESERVATION
The Product and set of operational documents are stored in preserved condition in Manu-
facturer’s packaging boxes.
The time of represervation – 2 years from the Manufacturer’s commissioning.
The preservation is done in full terms, for 2 years, applying protection and packaging.
The represervation is done in heated rooms in the same order as the preservation.
The represerved Product and documents are placed in package.