17
Version 0.1.1
Operating manual
Table 10 – Menu «Оборудование»
Position
№
Name
Description
1
ID
AHU network address
2
Имя
AHU name
3
Состояние
AHU status («Инициализация»
– initialization, «В работе» –
operating, «Предупреждение» – warning, «Тревога» – alarm)
4
Общ.Тест
To test all connected AHUs for operation errors
5
Общ.Сброс
To reset all removed errors of connected AHUs
6
To set up default parameters for all connected AHUs
7
To set up name and ID number for a new AHU
8
To edit heating parameters of the selected AHU
9
To delete the selected AHU
10
ОК
To return to the main screen
11
Отмена
To return to the main screen
Table 11 describes parameters which are displayed after pressing «
» button.
Table 11 – Description of parameters
Parameter
Default value
Описание
Имя
–
AHU name
(this line appears only while editing one AHU)
Задание t
зад
, °С
20.0
To set up required temperature inside dome (t
set
)
Нижняя граница
гистерезиса -t, °С
0.0
Heating will switch on when the temperature falls lower than
«t
set
– 0.0»
Верхняя граница
гистерезиса +t, °С
5.0
Heating will switch off when the temperature rises higher than
«t
зад
+ 5.0»
Нижняя допустимая
граница t
н
, °С
–40.0
If the temperature is lower than the specified one, THs are
switched on forcefully
Верхняя допустимая
граница t
в
, °С
70.0
If the temperature is higher than the specified one, THs are
switched off forcefully
Нижняя допустимая
граница I
н
, А
0.1
If current values of THs are lower than the specified ones,
alarm actuates
Верхняя допустимая
граница I
в
, А
10000.0
If current values of THs are higher than the specified ones,
alarm actuates