FIGURE 4—Vestibule Sequencing

Once the TDM has been wired for the above application, programming of the device is as follows:
1)  Apply power to the unit.  The display will flash double bars (

––

) indicating that the unit is in its normal 

 

operating ready mode.

2)  To begin programming, depress the 

PROGRAM MODE BUTTON

 one time.  The first parameter to be 

 

programmed will appear on the display.  This is the delay time, or "on time" of the output #1 and is 

 

displayed as 

d1

 followed by the time setting of 

2.0

 (Factory Setting) which indicates 2.0 seconds (It 

 

will flash between the two).  This is the time duration that you want the interior door to remain open 

 

(It's usually set around 4-5 seconds).  To adjust the time setting, use a small screwdriver and rotate 

 the 

DISPLAY ADJUSTMENT

 clockwise to increase and counterclockwise to decrease the time setting.  

 

After the desired value is displayed, depress the 

PROGRAM MODE BUTTON

 again to save the value.  

 

The display will now read 

d2

.  

d2

 is the delay time or "on time" of output #2.  This is the time setting 

 

that you want for the exterior door to remain open.  This is usually set around 4-5 seconds.  To adjust 

 

the setting, rotate the 

DISPLAY ADJUSTMENT

 until the desired value is displayed and then depress 

 the 

PROGRAM MODE BUTTON

.  The display should then read 

d3

.  This is the setting for the delay 

 

time between the activation of the interior door and the exterior door.  This time is usually set around 

 

1-4 seconds.  Again, adjust the setting and then depress the 

PROGRAM MODE BUTTON

.  The display 

 

should now read 

d4.

  This is the delay time between the opening of the doors going in the opposite 

 

direction.  Adjust this value in the same manner as before.  When the 

PROGRAM MODE BUTTON

 is 

 depressed, 

i1

 will then be displayed.  Now wait 30 seconds until the double bars (

––

) appear, 

 

indicating that the unit is in its normal operating ready mode.

3)  You are now ready to test your installation.  If any of the time settings need to be changed, make the 

 

change and press the 

PROGRAM MODE BUTTON

 once to save the new value.  Then wait 30 seconds

 

until the double bars (

––

) appear again, indicating that the unit is in its normal operating mode.

4)  During operation of the unit, the display will indicate its operating status.  Please refer to Figure 5 at 

 

the end of this installation manual.

PROGRAMMING 

PROCEDURE

MS SEDCO

TDM

Timing Control Module

12-24V

AC / DC

      Interior

Door Operator

      Control

     Exterior

Door Operator

     Control

N.O.

N.O.

Output #1

Output #2

GRAY

WHT

BROWN

YEL

GRN

GRN

Wall

Interior

Switch

PUSH

TO 

OPEN

BLU

WHT / BLU

Wall

Exterior

Switch

PUSH

TO 

OPEN

WHT / GRN

WHT / RED

WHT / VIO

WHT / GRAY

WHT / BROWN

switch that 

opens interior

door

opens exterior

door

These optional switches are 

mounted inside the vestibule

Jumper installed for 

   "DRY" contacts

input #1

input #2

input #4

input #3

TDM

INPUT 

4

INPUT 

3

INPUT 

2

INPUT 

1

12-24V AC/DC

INPUT 

1

COM

COM

COM

COM

N.

O.

N.

C.

N.

C.

N.

O.

PROGRAM

MODE BUTTON

DISPLAY

ADJUSTMENT

LED DISPLAY KEY

d1 = delay 1

d2 = delay 2

d3 = delay d1 to d2

d4 = delay d2 to d1

i1 = input 1 (n.o. / n.c.)

i3 = input 3 (n.o. / n.c.)

i2 = input 2 (n.o. / n.c.)

i4 = input 4 (n.o. / n.c.)

o2 = output 2 (n.o. / n.c.)

o1 = output 1 (n.o. / n.c.)

o1= dry

o1= wet

Output #1

Output #2

                             Universal Time Delay Module 

INSTALLATION INSTRUCTIONS

The 

Series

TDM

Commander

7898 Zionsville Road 

 Indianapolis, Indiana 46268

Telephone: (317) 842-2545 

 www.mssedco.com 

 [email protected]

Summary of Contents for TDM

Page 1: ...ns are included Figure 2 Simple Time Delayed Output Figure 3 Electric Lock Door Operator Sequencing Figure 4 Vestibule Door Sequencing Detailed Operating Display functions for the TDM are shown in Figure 5 For additional technical assistance contact us toll free at 1 317 842 2545 Figure 5 TDM Operating Display Function NOTICE These instructions are provided for your convenience Please verify your ...

Page 2: ...044 TDMv1017 FIGURE 1 TDM Layout Wiring Connections Input Connections Wht Brown Wht Vio Wht Grn Wht Red Wht Blue Blue Green Green Wht Gray Input Power 12 24V AC or DC Switch Input 1 Switch Input 2 Switch Input 3 Switch Input 4 Output Connections Orange Brown Yellow Violet White Gray Output 2 Output 1 COM N O N C COM N O N C Input Actions Input 1 Sequences Output 1 then Output 2 Input 2 Sequences O...

Page 3: ...hanged make the change to the d1 setting press the PROGRAM MODE BUTTON once and then wait 30 seconds until the double bars appear again 5 During operation of the unit the display will indicate its operating status Please refer to Figure 5 at the end of this installation manual or Electric Exit Device Wall Switch PUSH TO OPEN WHT RED WHT VIO MS SEDCO TDM Timing Control Module N C Output 1 Input 3 S...

Page 4: ...e door This time is usually set around 0 5 1 second Again adjust the setting and then depress the PROGRAM MODE BUTTON The display should now read d4 Now wait 30 seconds until the double bars appear indicating that the unit is in its normal operating ready mode NOTE d1 should be longer than d3 3 You are now ready to test your installation If any of the time settings need to be changed make the chan...

Page 5: ... is the delay time between the opening of the doors going in the opposite direction Adjust this value in the same manner as before When the PROGRAM MODE BUTTON is depressed i1 will then be displayed Now wait 30 seconds until the double bars appear indicating that the unit is in its normal operating ready mode 3 You are now ready to test your installation If any of the time settings need to be chan...

Page 6: ...o2 Relay Output 2 N O or N C Error flashing The PUSHBUTTON FAULT INDICATOR is a special feature designed to alert the installer if a pushbutton is stuck in the active position or if the wires have shorted If this occurs the display will flash double dots Additionally this could mean that the wiring did not match the programmed parameter In other words the unit may be programmed for use with a norm...

Reviews: