8 Maintenance and inspection
46
BA5789879-01 EN
Maintenance
The product is maintenance-free.
Inspection
Depending on the conditions of use of the device and the national regula-
tions in the respective country of use, the transformer manufacturers can
specify different inspection intervals.
► Observe the inspection intervals defined in CIGRE Publication No. 445
"Guide for Transformer Maintenance" or the inspection intervals specified
by the transformer manufacturer.
The following checks are necessary for
each
transformer inspection:
▪ Visual inspection for leakages, corrosion and damage
▪ Function test; see Commissioning [
In addition, the following checks are necessary during every
second
trans-
former inspection:
▪ Visual inspection for leakages, corrosion and damage
under
the cover
► To do so, remove the cover; see [
Section 5.1, Page 27]. (For OD cover
only: First remove the pipe connection of the oil escape opening; see
[
▪ Visual inspection of the compression spring
▪ Visual inspection of the flange
▪ Visual inspection of the switches
In the event of questions or irregularities, contact the Technical Service de-
partment:
Maschinenfabrik Reinhausen GmbH
MR Service & Complaint
Falkensteinstrasse 8
93059 Regensburg, Germany
E-mail: [email protected] or [email protected]