2:
Configure node:
Note! All 5 characters must be typed. See also chapter 3 for details
The meaning of each character as follows:
E D C B A Meaning
x
x
x
X
0
Sends alarms on changes from Non-active
to Active Di_1 to Di_6
X X X X
1
Sends alarms both on changes from Non-
active to Active and from Active to Non-
active Di_1 to Di_6
X X X
0
X Dial up alarms when Di_1 to Di_6 changes
X X X
1
X SMS alarms when Di_1 to Di_6 changes
X X
0
X X Disable SMS Control of switchgear status
X X
1
X X Enable SMS Control of switchgear status
X
0
X X X Use 2 analog inputs
X
1
X X X Use 4 analog inputs
3:
Set Actuator relay timeout:
Different types of actuators and switches require different relay timeout. Please set a
value appropriate for the switchgear to which your ComTroll 333 RTU is connected.
The time can be set in milliseconds in the range from 200 ms to 64000 ms.
5 numbers must be typed, as in the example below, where relay timeout is set to
500ms.
Default value is 30000ms.