Compact Unit Heater Venting Kit

Operating Instructions and Owner’s Manual

SHIPPING

The heater vent kit is shipped complete, with all necessary
components.  Check the components for damage.  The  

 

receiving party should contact the last carrier immediately  
if any shipping damage is found.

 

 

VENTING

A – GENERAL RECOMMENDATIONS AND 
REQUIREMENTS

NOTE:

 The vent is a passageway, vertical or nearly so, used to 

convey flue gases from an appliance, or its vent connector, to the 
outside atmosphere. The vent connector is the pipe or duct that 
connects a fuel-gas burning appliance to a vent or chimney. 

Unit heaters must be vented in compliance with all local codes 
or requirements of the local utility, the current standards of the 
(American) National Fuel Gas Code, ANSI Z223.1 or (Canada) 
CSA B149.1 Natural Gas and Propane Installation Code, and the 
following instructions. 

A metal stamped/extruded transition is supplied with this certified 
unit. It must not be modified or altered and must be installed 
on the outlet of the induced draft blower assembly prior to the 
installation of the vent or vent connector. Failure to comply with 
this requirement will void the certification of the unit by the 
approval agencies. All joints shall be secured with at least two 
corrosion resistant screws. All joints must be checked for gas 
tightness after installation. 

TABLE 2 

MAXIMUM VENT LENGTHS 

HORIZONTAL VENTS

 

No. of 

ft 

m

 

Elbows

 

25 

7.6

 

20 

6.1

 

15 

4.6

 

10 

3.0

 

1.5

Maximum length of vent connector not to exceed 30 ft. (9.1m).

B – VERTICAL VENTS USING METAL VENT 
PIPE – COMMERCIAL AND RESIDENTIAL 
INSTALLATIONS

MHU/HSU compact unit heaters are listed as Category I 
appliances for vertical vent installations. 

1.  MHU/HSU unit heaters are to be used with NFPA- or ANSI-

approved chimneys, U.L. listed type B-1 gas vents, single 
wall metal pipe, or listed chimney lining system for gas 
venting where applicable, as well as the modifications and 
limitations listed in 

Figure 2

. Seal single wall vent material 

according to the section 

A - General Recommendations 

and Requirements.

2.  The vent connector shall be 3” (76mm) diameter on 45 units. 

In all cases, a flue transition piece (supplied) is required to 
fit over the outlet of the induced draft assembly on the 
appliance. 

3.  Keep the vent connector runs as short as possible with 

a minimum number of elbows. Refer to the (American) 
National Fuel Gas Code ANSI Z223.1 or (Canada) CSA B149.1 
Natural Gas and Propane Installation Code for maximum 
vent and vent connector lengths. Horizontal run of the vent 
connector from the induced draft blower to the chimney/vent 
cannot exceed the values in 

table 2

4.  When the length of a single wall vent, including elbows, 

exceeds 5 feet (1.5m), the vent shall be insulated along 
its entire length with a minimum of 1/2” thick foil faced 

used in an unheated area it shall be insulated. Failure to do 
so will result in condensation of flue gases. 

5.  The unit may be vented vertically as a single appliance or as 

venting situations, vent connectors for other appliances 
must maintain a 4” (100mm) vertical separation between 
the vent connectors. Refer to common venting tables in the 
(American) National Fuel Gas Code ANSI Z223.1 or (Canada) 
CSA B149.1 Natural Gas and Propane Installation Code for 
proper vent size.

6.  Clearance to combustible material is 6” (152mm) for single 

wall vent material except where a listed clearance thimble is 
used. Clearance to combustible material for type B-1 vent or 
factory-built chimney is per manufacturer’s instructions.

7.  The vent connector shall be supported without any dips or 

sags. Vertical vents shall be supported in accordance with 
their listing and manufacturers’ instructions. All horizontal 
vent connector runs shall have a slope up to the vertical vent 
of at least 1/4” per foot (1mm per 50mm). 

8.  All vertical type B-1 vents, single wall vents, or listed chimney 

lining system must be terminated with a listed vent cap or 
listed roof assembly.

9.  The vent must extend at least 3’ (1m) above the highest point 

where it passes through a roof of a building and at least 2’ 
(0.6m) higher than any part of a building within a horizontal 
distance of 10’ (3.05m) unless otherwise specified by the 
(American) National Fuel Gas Code, ANSI Z223.1 or (Canada) 
CAN/CGA-B149 Installation Code. The vent must extend at 
least 5’ (1.6m) above the highest connected equipment flue 
collar. 

C – HORIZONTAL VENTING – GENERAL

Common venting is not allowed when horizontally venting the unit 
heater. 

The minimum horizontal vent length is three feet (914mm).  

1.  If possible, do not terminate the horizontal vent through a 

wall that is exposed to prevailing wind. Exposure to excessive 
winds can affect unit performance.

2.  Vent termination must be free from obstructions and at least 

12” (306mm) above grade level and maximum snow height.

Summary of Contents for Heatstar HSU45

Page 1: ... HEATSTAR COMPACT UNIT HEATER VENTING KIT MHU 45 MHU 75 WARNING Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier WARNING If the information in these instructions are not followed exactly a fire or explosion may result c...

Page 2: ...ENDED BY THE INSTRUCTIONS NEVER USE THE HEATER IN SPACES WHICH DO OR MAY CONTAIN VOLATILE OR AIRBORNE COMBUSTIBLES OR PRODUCTS SUCH AS GASOLINE SOLVENTS PAINT THINNER DUST PARTICLES OR UNKNOWN CHEMICALS WARNING COMBUSTION BY PRODUCTS PRODUCED WHEN USING THIS PRODUCT CONTAIN CARBON MONOXIDE A CHEMICAL KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER AND BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM WARN...

Page 3: ...ght Leak Tested ___________________________________ Motor Amps_ _____________________________________________________________ Furnace Btu Input_________________________________________________________ Line Pressure_____________________________________________________________ Manifold Pressure w c _ ____________________________________________________ Job No _______________________________________ ...

Page 4: ... possible with a minimum number of elbows Refer to the American National Fuel Gas Code ANSI Z223 1 or Canada CSA B149 1 Natural Gas and Propane Installation Code for maximum vent and vent connector lengths Horizontal run of the vent connector from the induced draft blower to the chimney vent cannot exceed the values in table 2 4 When the length of a single wall vent including elbows exceeds 5 feet...

Page 5: ...l pipe as shown in 12 inches from outside wall as shown in Figure 3 9 For horizontal venting the vent pipe shall be supported with hangers no more than 3ft 1m apart to prevent movement after installation D HORIZONTAL VENTING COMMERCIAL 1 Horizontal commercial installations are for buildings which are not attached to living spaces The vent may be single wall vent material installed according to the...

Page 6: ...pliance must never be connected to a chimney that is servicing a solid fuel appliance If a fireplace chimney flue is used to vent this appliance the fireplace opening must be permanently sealed 2 A fan assisted unit heater may be commonly vented into an existing lined masonry chimney provided The chimney is currently serving at least one draft hood equipped appliance The vent connector and chimney...

Page 7: ...cted to the common venting system If the venting system has been installed improperly the system must be corrected 1 Seal any unused openings in the common venting system 2 Visually inspect the venting system for proper size and horizontal pitch Determine there is no blockage or restriction leakage corrosion or other deficiencies which could cause an unsafe condition 3 If practical close all build...

Page 8: ......

Page 9: ...Operating Instructions and Owner s Manual Compact Unit Heater E 9 ...

Page 10: ...e foregoing is the full extent of the responsibility of the Company There are no other warranties express or implied Specifically there is no warranty of fitness for a particular purpose and there is no warranty of merchantability In no event shall the Company be liable for delay caused by imperfections for consequential damages or for any charges of the expense of any nature incurred without its ...

Page 11: ...ADVERTENCIA La instalación el ajuste la alteración la reparación o el mantenimiento indebidos pueden ocasionar daños a la propiedad o lesiones Consulte este manual Para obtener ayuda o información adicional consulte con un instalador calificado una agencia de reparación calificada o el suministrador de gas ADVERTENCIA Si no se sigue la información de estas instrucciones con exactitud puede produci...

Page 12: ... EN LAS INSTRUCCIONES NO UTILIZAR NUNCA EL CALENTADOR EN ESPACIOS QUE CONTENGAN O PUEDAN CONTENER COMBUSTIBLES VOLÁTILES O AEROTRANSPORTADOS O PRODUCTOS COMO GASOLINA SOLVENTES DILUYENTE PARA PINTURAS PARTÍCULAS DE POLVO O QUÍMICOS DESCONOCIDOS ADVERTENCIA LA COMBUSTIÓN GENERADA CUANDO SE UTILIZA ESTE PRODUCTO CONTIENE MONÓXIDO DE CARBONO UN QUÍMICO QUE EL ESTADO DE CALIFORNIA RECONOCE COMO CAUSAN...

Page 13: ...__________________________ Se comprobó que las conexiones de tuberías estén ajustadas y sin fugas ___________ Amperaje del motor_ ______________________________________________________ Potencia en Btu de la calefacción_____________________________________________ Presión de línea___________________________________________________________ Presión de colector w c _ __________________________________...

Page 14: ...dad de codos Para conocer las longitudes máximas de ventilación y conectores de ventilación consulte el Código Nacional de Gas Combustible de EE UU ANSI Z223 1 o el Código de Instalación de Gas Natural y Propano de Canadá CSA B149 1 El tendido horizontal del conector de ventilación entre el soplador de tiro inducido y la chimenea o ventilación no debe superar los valores de la tabla 2 4 Si la long...

Page 15: ...lgadas de la pared exterior como se muestra en la Figura 3 9 En una ventilación horizontal el tubo de ventilación debe sujetarse con barras de suspensión a no más de 3 pies 1 m de distancia para evitar el movimiento después de la instalación D VENTILACIÓN HORIZONTAL COMERCIAL 1 Las instalaciones horizontales de uso comercial son para edificios que no lindan con espacios residenciales La ventilació...

Page 16: ...ca deben conectarse a una chimenea usada para un artefacto de combustible sólido Si se utiliza la chimenea de un hogar se deberá sellar en forma permanente la abertura del hogar VENTILACIÓN HORIZONTAL INSTALACIÓN RESIDENCIAL PENDIENTE ASCENDENTE SOPLADOR DE TIRO INDUCIDO 12 PULGADAS MÍN 30 5 CM TAPA DE TERMINACIÓN DE VENTILACIÓN DISTANCIADOR HOMOLOGADO A TRAVÉS DE PARED COMBUSTIBLE PUEDE SELLARSE ...

Page 17: ...o está en funcionamiento y el resto apagado pero conectado al sistema de ventilación común Si el sistema de ventilación se instaló de forma incorrecta se deberá corregir 1 Selle todas las aberturas no utilizadas del sistema de ventilación común 2 el tamaño y el declive correctos Determine que no haya obstrucción o restricción fugas corrosión u otras fallas que puedan causar una situación insegura ...

Page 18: ... De Respiradero De Gas De 4 1 2 02917 Collar Storm De 4 1 3 02918 Lamina Protectora De Techo Ajustable De 4 1 4 02912 Manquito Protectot De Pared Ajustable De 4 1 5 02914 Codo De 4 90 Grados 1 6 02913 Tubo De Descarga Desfogue De 4 x24 2 7 02911 Tubo De Descarga Desfogue En B De 4 x36 1 8 02916 Adaptador De 3 A 4 1 ...

Page 19: ...Instrucciones de funcionamiento y manual del usuario S 9 Calentador compacto ...

Page 20: ...reclamo Además infórmenos la fecha de compra y el nombre y la dirección del vendedor del producto La información precedente constituye el alcance total de la responsabilidad de la Empresa No existe ningún otro tipo de garantía explícita ni implícita En particular no existen garantías de aptitud para un fin específico ni de comercialización La Empresa no será responsable en ninguna circunstancia po...

Page 21: ...ATER HEATSTAR CHAUFFAGE D UNITE COMPACT DECHARGEANT LE KIT MHU 45 MHU 75 AVERTISSEMENT toute installation réglage modication réparation ou entretien inapproprié peut causer des blessures ou des dommages matériels Veuillez consulter ce guide d utilisation Pour obtenir de l aide ou des renseignements complémentaires consultez un installateur qualifié un fournisseur de services d entretien ou la comp...

Page 22: ...EIL DE CHAUFFAGE DANS UN LOCAL QUI CONTIENT OU EST SUSCEPTIBLE DE CONTENIR DES PARTICULES COMBUSTIBLES EN SUSPENSION DANS L AIR OU DES PRODUITS TELS QUE DE L ESSENCE DES SOLVANTS DU DILUANT À PEINTURE DES PARTICULES DE POUSSIÈRE OU DES PRODUITS CHIMIQUES INCONNUS AVERTISSEMENT L UTILISATION DE CET APPAREIL GÉNÈRE DES SOUS PRODUITS DE COMBUSTION CONTENANT DU MONOXYDE DE CARBONE UN PRODUIT CHIMIQUE ...

Page 23: ...________________________________________ Branchements de la conduite de gaz bien serrés et fuites recherchées ______________ Intensité électrique du moteur_______________________________________________ Puissance de l appareil de chauffage BTU _____________________________________ Pression de la conduite_____________________________________________________ Pression d admission d eau_______________...

Page 24: ... évent ne peut dépasser les valeurs indiquées au tableau 2 4 Lorsque la longueur d un évent à paroi simple coudes inclus dépasse 1 5 m 5 pi celui ci doit être isolé dans toute sa longueur à l aide d un mm 1 2 po d épaisseur à densité de 38 1 mm 1 1 2 po Si un évent à paroi simple est utilisé dans une aire non chauffée il doit être isolé Si vous ne prenez pas cette précaution il se produira une con...

Page 25: ...chéisez le joint entre le tuyau à paroi simple et celui à paroi double et l espace annulaire du tuyau 2 Le bord intérieur du té d extrémité de l évent doit être d au moins 30 5 cm 12 po à partir du mur externe comme illustré à la FIgure 3 9 Pour la ventilation horizontale le tuyau d évent doit être soutenu par des supports espacés de 1 m 3 pi maximum pour éviter tout mouvement une fois l installat...

Page 26: ...écialement conçus Les cheminées en maçonnerie non chemisées sont interdites Ne raccordez jamais un appareil de Catégorie 1 à une cheminée desservant un appareil à combustible solide Si vous utilisez un conduit de cheminée de foyer pour ventiler l appareil de chauffage VENTILATION HORIZONTALE INSTALLATION RÉSIDENTIELLE PENTE ASCENDANTE VENTILATEUR À TIRAGE INDUIT 30 5 CM MIN 12 PO CAPUCHON D EXTRÉM...

Page 27: ...ant que les autres appareils ne sont pas en fonction mais toujours connectés au système de ventilation commune L appareil testé doit être lui en fonction Si le système de ventilation a été mal installé il faudra corriger la situation 1 Bouchez toutes les ouvertures non utilisées du système de ventilation commune 2 Faites une inspection visuelle du système de ventilation pour déterminer la dimensio...

Page 28: ...nt Ref Item Description Qty 1 06430 Capuchon 4 De Ventilation De Gaz 1 2 02917 Mitre 4 1 3 02918 Solin De Toit Reglable 4 1 4 02912 Emboitement Mural Reglable 4 1 5 02914 Coude De 4 A 90 1 6 02913 Tuyau D event 4 x 24 2 7 02911 Tuyau D event De Type B 4 x 36 1 8 02916 Adaptateur 3 Sur 4 1 ...

Page 29: ...Guide d utilisation et instructions de fonctionnement Appareils de chauffage compacts F 9 ...

Page 30: ...amation Indiquez nous également la date d achat et le nom et l adresse du détaillant de qui vous avez acheté le produit Ce qui est énoncé ci dessus constitue la responsabilité totale de l entreprise Il n existe aucune autre garantie expresse ou tacite Plus précisément il n y a aucune garantie concernant l adéquation à une utilisation particulière ni aucune garantie concernant la qualité marchande ...

Reviews: