Mr. Heater, Inc. | Kerosene Forced Air Heater

Operating Instructions and Owner’s Manual

Model 

MH125KTR, MH175KTR and MH210KTR

 heaters are equipped with a diagnostic control board and flashing LED error indicator. This 

flashing LED signals indicate unit operation status. See the following diagnostic guide for unit status and corrective action if necessary.

DIAGNOSTIC SAFETY SHuTDOWN AND TROuBlE SHOOTING

lED

uNIT OpERATION

TROuBlE SHOOTING

Steady ON

System Check

System performing self test. No action required.

Steady OFF

Operation OK

No action required.

2 Flashes

No flame detected

Heater fails to start during the first 30 sec. of operation.

Check wiring to motor (per wiring schematic in manual).

1. 

Make sure that the pressure gauge is in place and not damaged.

2. 

Adjust pressure for proper heater operation per manual.

3. 

With heater disconnected from AC source, rotate fan clockwise to verify motor is free.

4. 

Remove air filter housing from motor and inspect the pump rotor for damage. If damaged, replace rotor assembly.

5. 

If wiring is correct, pump rotor is okay, and motor is not rotating freely, replace motor or power-pack assembly.

6. 

If problem persists, replace oil flame control assembly.

7. 

Check for spark arching from the electrode assembly (ref. 50), to the combustion cylinder (ref. 39).

8. 

Check the cad cell (ref. 38) for 

9. 

continuity.

3 Flashes

High limit switch 
failure

Make sure heater is cooled off, press reset switch and retry.

1. 

4 Flashes

CAD Cell Failure

Check wiring to cad cell (per wiring schematic in manual).

1. 

Clean cad cell photo cell.

2. 

Slide cad cell out of cad cell holder.

• 

Push the photo cell out of the black rubber cad cell housing by pushing on the 2 purple wires.

• 

Clean the photo cell with a soft cloth and rubbing alcohol.

• 

Pull the photo cell back into the cad cell housing and reinstall into holder.

• 

Test heater.

• 

If the heater still does not operate, replace cad cell.

3. 

Replace oil flame control assembly.

4. 

Power Light

Power to control

Sensing power. No action required.

1. 

Model 

MH50KR and MH75KTR 

heaters are NOT equipped with a diagnostic control board or flashing LED error indicator. See the following 

troubleshooting guide for unit status and corrective action if necessary.

SYMpTOM 

 

TROuBlE SHOOTING 

 
High limit switch Open Circuit 

1)  Make sure heater is cooled off, toggle switch to “OFF” position, wait 5 minutes and retry.

 

 

 

Sparks, calling for flame, but 

1)  Check wiring to motor (per wiring schematic in manual).

no or slow motor operation 

2)  Make sure that the pressure gauge is in place and not damaged.

 

 

3)  Adjust pressure for proper heater operation per manual.

 

 

4)  With heater disconnected from AC source, rotate fan clockwise to verify motor is free.

 

 

5)  Remove air filter housing from motor and inspect the pump rotor for damage. If damaged, replace rotor assembly.

 

 

6)  If wiring is correct, pump rotor is okay, and motor is not rotating freely, replace motor or power-pack assembly.

 

 

7)  If problem persists, replace oil flame control assembly.

 

 

8)  Check for spark arching from the electrode assembly, to the combustion cylinder.

 

 

9)   Check the cad cell for 

continuity.

No Spark 

 

1)  

Check length and gage of extension cord for proper amp. draw. (Check requirements on page 4.)

 

 

2)  Check wiring to igniter (per wiring schematic in manual).

 

 

3)  Check gap between electrode probes (2.3 - 3 mm).

 

 

4)  Still no spark, replace igniter assembly.

 

 

5)  Replace oil flame control assembly.

Abnormal Motor Operation - 

1)  Motor speed too low (Motor should operate at 3450rpm) - Replace motor. 

Motor overheats or Stops 

2)  With heater disconnected from AC source, rotate fan clockwise to verify motor is free.

 

 

3)  Remove air filter housing from motor and inspect the pump rotor for damage. If damaged, replace rotor  

 

 

 

assembly.

 

 

4)  If wiring is correct, pump rotor is okay, and motor is not rotating freely, replace motor or power-pack assembly.

 

 

5)  Replace oil flame control assembly.

Unable to Detect Flame 

1)  Check wiring to cad cell (per wiring schematic in manual).

 

 

2)  Clean cad cell photo cell.

 

 

 

a)   Slide cad cell out of cad cell holder.

 

 

 

b)   Push the photo cell out of the black rubber cad cell housing by pushing on the 2 purple wires.

 

 

 

c)  

Clean the photo cell with a soft cloth and rubbing alcohol.

 

 

 

d)   Pull the photo cell back into the cad cell housing and reinstall into holder.

 

 

 

e)   Test heater.

 

 

3)  If the heater still does not operate, replace cad cell.

 

 

4)  Replace oil flame control assembly.

Flame Control Failure 

1)  Check wiring in heater (per wiring schematic in manual).

 

 

2)  Replace oil flame control assembly.

Summary of Contents for 125KTR

Page 1: ...ed portable heater It uses air oxygen from the area in which it is used Adequate combustion and ventilation air must be provided Refer to page 3 KEROSENE FORCED AIR HEATER UL 733 CSA CAN3 B140 9 3 03...

Page 2: ...D USE OR SERVICE THIS HEATER IF YOU NEED ASSISTANCE OR HEATER INFORMATION SUCH AS AN INSTRUCTIONS MANUAL LABELS ETC CONTACT THE MANUFACTURER WARNING FIRE BURN INHALATION AND EXPLOSION HAZARD KEEP SOLI...

Page 3: ...ns and instructions and of the hazards involved SAFETY PRECAUTIONS 1 Recommended for use with No 1 K kerosene fuel Factory tested for use with No 2 K kerosene No 1 or No 2 Diesel No 1 or No 2 fuel oil...

Page 4: ...ater from power source MH75KTR MH125KTR MH175KTR MH210KTR Push On Off switch to Off position For extended shutdown unplug heater from power source RESTART AFTER SAFETY SHUTDOWN MH50KR MH75KTR MH125KTR...

Page 5: ...solid object to remove contaminates Compressed air or liquids should not be used to clean this filter Reinstall cleaned filter in filter body in the same position as it was when removed If the filter...

Page 6: ...wing troubleshooting guide for unit status and corrective action if necessary SYMPTOM TROUBLE SHOOTING High limit switch Open Circuit 1 Make sure heater is cooled off toggle switch to OFF position wai...

Page 7: ...SET MOTOR CAPACITOR CIRCUIT BOARD 18AWG YELL 18AWG YELL 18AWG RED 18AWG RED 18AWG WHT 18AWG BLK 18AWG GRN 18AWG PURPLE 18AWG PINK 18AWG PINK 1 2 3 4 5 6 18AWG PURPLE THERMOSTAT 18AWG BLUE 7 8 ELECTR0...

Page 8: ...ert 19 26898 26898 26898 26898 Receptacle 110V 20 22104 22104 22104 22104 AC Receptacle Cover 21 26833 26833 26833 26833 26833 Air Pump Cylinder 22 21810 21810 21810 21810 21810 Outlet Housing 23 2181...

Page 9: ...ions and Owner s Manual Kerosene Forced Air Heater Model MH50KR MH75KTR MH125KTR MH175KTR MH210KTR 1 2 3 4 5 6 7 9 10 1 1 13 14 15 16 17 18 19 20 21 24 25 Filter Kit 26 53 28 29 30 31 32 34 35 36 37 3...

Page 10: ...dealer or direct from the factory FOR INFORMATION REGARDING SERVICE Please call Toll Free 800 251 0001 www mrheater com Our office hours are 8 30 AM 5 00 PM EST Monday through Friday Please include t...

Reviews: