DCA36SPXU4F • OPERATION MANUAL — REV. #4 (09/18/19) — PAGE 31
DANGER
Before connecting this generator to any
building’s electrical system, a
licensed
electrician
must install an
isolation
(transfer) switch.
Serious damage to
the building’s electrical system may occur
without this transfer switch.
NOTICE
When connecting the generator to a isolation (transfer)
switch,
ALWAYS
have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
NOTICE
When the
Auto Off/Reset Manual
switch is placed
in the
AUTO
mode, the generator will
automatically
start
in the event of commercial power falling below a
prescribed level by means of a contact closure that is
generated automatically by a transfer switch.
In this position (
AUTO)
, should an outage occur, the
automatic transfer switch (ATS) will start the generator
automatically via the generator's auto-start contacts
connected to the ATS's start contacts.
Please refer to your ATS installation manual for further
instructions for the correct installation of the auto-start
contacts of the generator to the ATS.
WARNING
When running the generator in the
AUTO
mode,
remember the generator can start up at any time without
warning.
NEVER
attempt to perform any maintenance
when the generator is in the auto mode.
NOTICE
When the
Auto Off/Reset Manual
switch is placed
in the
AUTO
position, the engine glow plugs will be
warmed and the engine will start automatically.
STARTING (AUTO MODE
When starting generator in
AUTO
mode use the “Manual
Start-up” procedure except where noted (see below).
1. Perform steps 1 through 5 in the Before Starting section
as outlined in the Manual Starting Procedure.
2. Place the
Auto Off/Reset Manual Switch
in the
AUTO
position.
Figure 40.
Auto Off/Reset Manual
Switch (AUTO)
3. Continue operating the generator as outlined in the
Manual Start-up procedure (start at step 7).
NOTICE
The engine speed switch
must
be set to the “High”
position when running in the
auto-start
mode. Failing
to set the switch in the proper position can result in
damage to your generator when it turns on.
GENERATOR START-UP PROCEDURE (AUTO MODE)
Summary of Contents for Whisperwatt DCA36SPXU4F
Page 2: ...PAGE 2 DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 PROPOSITION 65 WARNING ...
Page 41: ...DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 PAGE 41 GENERATOR WIRING DIAGRAM ...
Page 42: ...PAGE 42 DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 ENGINE WIRING DIAGRAM ...
Page 43: ...DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 PAGE 43 BATTERY CHARGER WIRING DIAGRAM ...
Page 44: ...PAGE 44 DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 JACKET WATER HEATER WIRING DIAGRAM ...
Page 45: ...DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 PAGE 45 NOTES ...