DCA36SPXU4F • OPERATION MANUAL — REV. #4 (09/18/19) — PAGE 23
OUTPUT TERMINAL PANEL CONNECTIONS
UOV TERMINAL OUTPUT VOLTAGES
240/120V outout voltages can be obtained using the
output
terminal lugs
.
The voltage regulator (VR), Figure 14 allows the user to
increase or decrease the selected voltage.
1Ø-240 Output Terminal Voltage
1. Connect the load wires to the output terminal lugs as
shown in Figure 13.
Figure 13. Output Terminal Lugs
1Ø-240V Connections
2. Turn the voltage regulator knob (Figure 14) clockwise
to increase voltage output, turn counterclockwise to
decrease voltage output. Use voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required.
Figure 14. Voltage Regulator Knob
U
O
V
BLACK
RED
WHITE
GREEN
GROUND
CONNECTION
BE USED
AT ALL TIMES
MUST
240V
SINGLE-PHASE
240 VAC (LOAD CONNECTIONS)
1Ø-120 Output Terminal Voltage Voltage
1. Connect the load wires to the output terminal lugs as
shown in Figure 15.
Figure 15. Output Terminal Lugs
1Ø-120V Connections
2. Turn the voltage regulator knob (Figure 14) clockwise
to increase voltage output, turn counterclockwise to
decrease voltage output.
U
O
V
BLACK
RED
WHITE
GREEN
GROUND
CONNECTION
BE USED
AT ALL TIMES
MUST
SINGLE-PHASE
120 VAC (LOAD CONNECTIONS)
120V
120V
NOTICE
ALWAYS
make sure that the connections to the UOV
terminals are
secure
and
tight
. The possibility of arcing
exists, that could cause a fire.
Summary of Contents for Whisperwatt DCA36SPXU4F
Page 2: ...PAGE 2 DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 PROPOSITION 65 WARNING ...
Page 41: ...DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 PAGE 41 GENERATOR WIRING DIAGRAM ...
Page 42: ...PAGE 42 DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 ENGINE WIRING DIAGRAM ...
Page 43: ...DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 PAGE 43 BATTERY CHARGER WIRING DIAGRAM ...
Page 44: ...PAGE 44 DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 JACKET WATER HEATER WIRING DIAGRAM ...
Page 45: ...DCA36SPXU4F OPERATION MANUAL REV 4 09 18 19 PAGE 45 NOTES ...