PAGE 18 — DCA125SSIU 50 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (12/22/08)
GENERATOR CONTROL PANEL
Generator Control Panel
Figure 4.
A
V
HZ
OFF
W
U
V
OFF
W-U
V-W
U-V
DECREASE
INCREASE
AUTO
MANUAL
OFF/RESET
LOW OIL PRESSURE
HIGH COOLANT TEMPERATURE
OVERCRANK
OVERSPEED
ENGINE RUNNING
MOOOOO-20001Q
1
2
3
4
5
7
6
The defi nitions below describe the controls and functions
of the DCA125SSIU Generator Control Panel (Figure 4).
Main Circuit Breaker
1.
—This three-pole, 300A main
breaker is provided to protect the the U,V, and W Output
Terminal Lugs from overload.
Voltage Regulator Control
2.
— Allows ±15% manual
adjustment of the generator’s output voltage.
Ammeter Change-Over Switch
3.
— This switch allows
the AC ammeter to indicate the current fl owing to the
load connected to any phase of the output terminals,
or to be switched off. This switch does not effect the
generator output in any fashion, it is for current reading
only.
Voltmeter Change-Over Switch
4.
— This switch allows
the AC voltmeter to indicate phase to phase voltage
between any two phases of the output terminals or to
be switched off.
Frequency Meter
5.
— Indicates the output frequency
in hertz (Hz). Normally 50 Hz.
AC Ammeter
6.
— Indicates the amount of current the
load is drawing from the generator per leg selected by
the ammeter phase-selector switch.
AC Voltmeter
7.
— Indicates the output voltage present
at the U,V, and W Output Terminal Lugs.
Located behind the generator control panel is the Generator
Control Box. This box contains some of the necessary
electronic components required to make the generator
function.
The Control Box is equipped with the following major
components:
Over-Current Relay
Automatic Voltage Regulator (AVR)
Starter Relay
Current Transformer
Voltage Selector Switch
Main Circuit Breaker
NOTICE
Remember the
overcurrent relay
monitors the current
fl owing from the
U,V, and W Output Terminal Lugs
to the load.
In the event of a short circuit or over current condition,
it will automatically trip the 300 amp main breaker.
To restore power to the
Output Terminal Panel
, press
the reset button on the overcurrent relay and place the
main
circuit breaker in the
closed
position (
ON
).
Summary of Contents for WHISPERWATT DCA125SSIU
Page 19: ...DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 PAGE 19 NOTES ...
Page 54: ...PAGE 54 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 GENERATOR ASSY ...
Page 56: ...PAGE 56 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 CONTROL BOX ASSY ...
Page 58: ...PAGE 58 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 CONTROL BOX ASSY ...
Page 60: ...PAGE 60 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 CONTROL BOX ASSY ...
Page 68: ...PAGE 68 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 BATTERY ASSY ...
Page 70: ...PAGE 70 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 MUFFLER ASSY ...
Page 72: ...PAGE 72 DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 FUEL TANK ASSY ...
Page 87: ...DCA125SSIU 50 HZ GENERATOR OPERATION AND PARTS MANUAL REV 0 12 22 08 PAGE 87 NOTES ...