DCA-300SSK III — PARTS AND OPERATION MANUAL (FEMA) — REV. #1 (05/07/03) — PAGE 31
2. Connect the load wires to the UVWO terminals as shown
in Figure 27.
DCA-300SSK III — OUTPUT TERMINAL PANEL CONNECTIONS
3Ø-480V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 480V operation
as shown in Figure 26. This configuration uses 6 jumper
plates in 3 different positions. Remember there are 2
jumper plates at every position. Every jumper plate
must
be used.
Figure 26. Voltage Change-Over Board
480V
Configuration
Figure 27. UVWO Terminal Lugs
3Ø-480V Connections
1Ø-480V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 480V operation as shown in Figure 26.
2. Connect the load wires to the UVWO terminals as shown
in Figure 28.
1Ø-277V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered
for 480V operation as shown in Figure 26.
2. Connect the load wires to the UVWO terminals as shown
in Figure 29.
Figure 29. UVWO Terminal Lugs
1Ø-277V Connections
ALWAYS
make sure that the
connections to the UVWO
terminals are
secure
and
tight
.
The possibility of arcing exists,
that could cause a fire.
NOTE
NEVER
attempt to connect a load to the
U V W O
output terminals while the
generator is operating. The possibility
exists of serious injury, electrical shock,
electrocution even death.
DANGER
DANGER
DANGER
DANGER
DANGER
:
Figure 28. UVWO Terminal Lugs
1Ø-480V Connections
Summary of Contents for DCA-300SSK III Series
Page 2: ...PAGE 2 DCA 300SSK III PARTS AND OPERATION MANUAL FEMA REV 1 05 07 03 ...
Page 7: ...DCA 300SSK III PARTS AND OPERATION MANUAL FEMA REV 1 05 07 03 PAGE 7 NOTE PAGE ...
Page 41: ...DCA 300SSK III PARTS AND OPERATION MANUAL FEMA REV 1 05 07 03 PAGE 41 NOTE PAGE ...
Page 53: ...DCA 300SSK III PARTS AND OPERATION MANUAL FEMA REV 1 05 07 03 PAGE 53 NOTE PAGE ...
Page 103: ...DCA 300SSK III PARTS AND OPERATION MANUAL FEMA REV 1 05 07 03 PAGE 103 NOTE PAGE ...