![mpec SA380-IT User Manual Download Page 52](http://html1.mh-extra.com/html/mpec/sa380-it/sa380-it_user-manual_1843052052.webp)
6
DC Monitored Circuit
DC monitored circuits show circuit voltage
and equivalent resistance to earth of each
circuit leg (R
B
and R
N
).
7
Earth Loop Resistance
The resistance between FE and Loop Earth
terminals.
8
Current Test
Displays the test currently being performed
by the device at the moment the page
refreshed.
Technicians Mode
Clicking on the white region of a monitored
circuit or earth loop display will cause the
device to enter
for that
Technicians Mode
particular circuit.
Missing Circuits
Only monitored circuits configured for
measurement are displayed.
Green Text
..is used to denote monitored circuits where
resistance to earth is
the defined
above
alert thresholds.
..is used to denote that earth loop
resistance is
the defined alert
below
threshold.
Orange Text
..is used to denote monitored circuits
suffering from a recoverable device
interlock.
Red Text
..is used to denote monitored circuits where
resistance to earth is
the defined
below
alert thresholds.
..is used to denote that earth loop
resistance is
above the defined alert
threshold.
..is used to denote monitored circuits
suffering from an unrecoverable device
interlock.
4.4.3 Technicians Modes