Wiring the Relay Output
The VPort 464 has two sets of relay output, relay 1 and relay 2, which are
located on the two 5-pin terminal block connectors. Each relay output
consists of the 3 contacts of the terminal block on the VPort 464’s top
panel. The relay output can be set up for:
1.
System alarm: Power failure, Video loss and Network disconnected.
2.
Event alarm: VMD (Video Motion Detection) and Digital Inputs.
ATTENTION
The current and power capacity of the relay output is a maximum
of 24 VDC @ 1A. You should be careful not to exceed this power
specification.
Wiring the Digital Inputs
VPort 464 has four sets of digital input, DI1, DI2, DI3 and DI4. Each DI
consists of two contacts of the 8-pin terminal block connector on VPort’s
top panel. The top view of one of the terminal block connectors is shown
here.
STEP 1:
Insert the negative (ground)/positive DI
wires into the
┴
/I1 terminals.
STEP 2:
To keep the DI wires from pulling loose, use
a small flat-blade screwdriver to tighten the
wire-clamp screws on the front of the terminal block
connector.
STEP 3:
Insert the plastic terminal block connector
prongs into the terminal block receptor, which is
located on the VPort 464’s top panel.
Communication Connections
VPort 464 models have one RJ45 console port (RS-232 interface), and 2
10/100/1000BaseT(X) Ethernet ports.