![Moxa Technologies PT-G7728 User Manual Download Page 39](http://html.mh-extra.com/html/moxa-technologies/pt-g7728/pt-g7728_user-manual_1842658039.webp)
PT-G7828/G7728
Featured Functions
3-27
First priority: MAC.ini
Second priority: Sys.ini
If no matching configuration file is found, the fault LED light will turn on, and the switch will boot up
normally.
NOTE
MAC.ini is named using the last 6 digits of the switch’s MAC address, without spaces.
5.
Auto backup to ABC-02 when configuration changes
Select the
Auto backup to ABC-02 when configuration change
checkbox and then click
Apply
. This
function is disabled by default.
The ABC-02 is capable of backing up switch configuration files automatically. While the ABC-02 is plugged
into the switch, enable the
Auto backup to ABC-02 when configuration change
option, and then click
Apply
. Once this configuration is modified, the switch will back up the current configuration to the
/His_ini
folder on the ABC-02. The file name will be the system date/time (MMDDHHmm.ini).
NOTE
MM=month, DD=day, HH=hour, mm=minutes, from the system time.
Log File Backup
There are three ways to back up Moxa switch’s log files: from a local drive, by remote TFTP server, or with Auto
Backup Configurator (ABC-02).
Local
Click the
Backup
button to back up the log file to a local drive.
TFTP Server
Enter the TFTP Server’s IP address and file name and then click the Backup button.
Auto Backup Configurator (ABC-02)
Click
Backup
to save the configuration file to the ABC-02. The file will be saved in the ABC-02’s
Moxa
folder
with filename
Sys.ini
.
Auto backup of event log to prevent overwrite
This function is designed to maintain a long-term record of the switch’s log files. Moxa Ethernet switches are
capable of saving 1000 event log entries. When the 1000-entry storage limit is reached, the switch will delete
the oldest saved event log. The ABC-02 can be used to back up these event logs. When the number of switch
log entries reaches 1000, the ABC-02 will save the oldest 100 entries from the switch.
Enable the
Auto backup of event log to prevent overwrite
, and then click
Apply
. After that, when the
ABC-02 is plugged into the switch, the event logs will always be saved to the ABC-02 automatically when the
number of switch log entries reaches 1000. Each backup action saves the oldest 100 logs to the ABC-02 in one
file, with the filename generated by the current system time as
MMDDHHmm.ini
. The file is saved to the
His_log
folder.
www.ipc2u.ru
www.moxa.pro