- 5 - 

LED Indicators 

Labeling  Indication  Description 

Status 

Status 

Green: Module ready 
Green Slow Blinking: Booting up 
Green Fast Blinking: Locating 
Red: Module error 
Red Slow Blinking: Upgrading firmware 
Red Fast Blinking: Safe mode (output module 
only) 
Off: Power off 

I/O 
Channel 

Channel 
Status 

Please refer to the ioThinx 4500 Series User’s 
Manual 

Module Configuration 

Please refer to the ioThinx 4500 Series User’s Manual. 

Specifications 

Input Current 

Varies per module; please refer to the datasheet 

Input Voltage 

System power: 

 

3.3 V, via the ioThinx 4510/4533, 45MR-7210 

Field Power: 

 

12/24 V, via the ioThinx 4510/4533, 45MR-7210 

 

DO modules (45MR-2600/2601/2606) must use 
an external power supply for field power 

Operating 
Temperature 

Standard Models: -20 to 60°C (-4 to 140°F) 
Wide Temp. Models: -40 to 75°C (-40 to 167°F) 

Storage 
Temperature 

-40 to 85°C (-40 to 185°F) 

Attention 

1.

 

This device is only for indoor use in environments with pollution 
degree 2. 

2.

 

The 45M has a ground pin on the back of the device. For surge 
protection, connect the DIN rail to earth ground. 

3.

 

Cables rated for a minimum temperature of 105°C must be used 
for the Power Supply Terminal. 

4.

 

We suggest using the following cable types for wiring: 

 

45MR-7210: 
> AWG 12 to 16 for power connections 

 

45MR-2600/2601/2606 Digital Output Terminals: 
> AWG 16 to 18 

 

45MR-2404 Relay Output Terminal: 
> AWG 16 to 18 

 

All other 45MR modules: 
> AWG 16 to 24 

 

Moxa Inc. 
Fl.4, No. 135, Lane 235, Baoqiao Rd. 
Xindian Dist., New Taipei City, Taiwan R.O.C. 

Summary of Contents for ioThinx 4500 Series

Page 1: ... Moxa Americas Toll free 1 888 669 2872 Tel 1 714 528 6777 Fax 1 714 528 6778 Moxa China Shanghai office Toll free 800 820 5036 Tel 86 21 5258 9955 Fax 86 21 5258 5505 Moxa Europe Tel 49 89 3 70 03 99 0 Fax 49 89 3 70 03 99 99 Moxa Asia Pacific Tel 886 2 8919 1230 Fax 886 2 8919 1231 Moxa India Tel 91 80 4172 9088 Fax 91 80 4132 1045 2019 Moxa Inc All rights reserved ...

Page 2: ...e head CPU module making sure that the upper and lower rails are hooked together Step 2 Align the 45M module side by side with the head CPU module and then push the 45M module until it touches the DIN rail Next apply more force until the module clips to the DIN rail NOTE After the module is firmly attached to the DIN rail the module connections to the internal bus will be established ...

Page 3: ...e lower part of the module Step 2 Push the top of the release tab to latch it and then pull the module out NOTE Electrical connections for the internal bus will be disconnected when removing the 45M module WARNING Be sure the power is off before removing modules to avoid damaging the equipment ...

Page 4: ...stallation Before installing the device make sure there is enough space between the device and nearby items walls other devices etc to ensure proper heat dissipation To ensure that the device works properly we suggest reserving the amount of space indicated in the adjacent figure CAUTION DO NOT install the device vertically If the device is installed vertically the fanless heat dissipation design ...

Page 5: ... 45MR 2600 2601 2606 must use an external power supply for field power Operating Temperature Standard Models 20 to 60 C 4 to 140 F Wide Temp Models 40 to 75 C 40 to 167 F Storage Temperature 40 to 85 C 40 to 185 F Attention 1 This device is only for indoor use in environments with pollution degree 2 2 The 45M has a ground pin on the back of the device For surge protection connect the DIN rail to e...

Reviews: