Industrial I/O

Specifications

84

124

132

27

27.8

Dimensions (unit = mm)

Side View

Front View

Rear View

Top View

Down View

LAN

Ethernet:

 2 x 10/100 Mbps switch ports, RJ45

Protection:

 1.5 KV magnetic isolation

Protocols:

 Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP

Analog Input 

(for ioLogik E1240)

Type:

 Differential input

Resolution:

 16 bits

I/O Mode:

 Voltage / Current

Input Range:

 0 to 10 VDC, 4 to 20 mA

Accuracy:

  

±0.1% FSR @ 25°C 
±0.3% FSR @ -10 and 60°C

Sampling Rate (all channels):

 12 samples/sec

Input Impedance:

 10M ohms (minimum)

Built-in Resistor for Current Input:

 120 ohms

Digital Input 

(for ioLogik E1210/E1212/E1214)

Sensor Type:

 NPN, PNP, and Dry contact

I/O Mode:

 DI or Event Counter

Dry Contact:

 

• Logic 0: short to GND

 

• Logic 1: open
Wet Contact:

 

• Logic 0: 0 to 3 VDC

 

• Logic 1: 10 to 30 VDC (DI COM to DI)
Isolation:

 3K VDC or 2K Vrms

Counter/Frequency:

 250 Hz, power off storage

Digital Output 

(for ioLogik E1211/E1212)

I/O Mode:

 DO or Pulse Output (up to 500 Hz) 

Pulse Wave Width/Frequency:

 1 ms/500 Hz

Over-voltage Protection:

 45 VDC

Over-current Limit:

 600 mA per channel

Over-temperature Shutdown:

 175°C (typical), 150°C (min.)

Output Current Rating:

 Max. 200 mA per channel

Isolation:

 3K VDC or 2K Vrms

Relay Output 

(for ioLogik E1214)

Type:

 Form A (N.O.) relay outputs, 5A

Contact Rating:

 5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110 VAC

Inductance Load:

 2 A

Resistance Load:

 5 A

Breakdown Voltage:

 500 VAC

Relay On/Off Time:

 1500 ms (Max.)

Initial Insulation Resistance:

 1G min. @ 500 VDC

Expected Life:

 100,000 times (Typical)

Initial Contact Resistance:

 30 milli-ohms (Max.)

Pulse Output:

 0.3 Hz at rated load

Power Requirements

Power Input:

 24 VDC nominal, 12 to 36 VDC

Power Consumption:

 130 mA typical @ 24 VDC

Physical Characteristics 

Wiring:

 I/O cable max. 14AWG

Dimensions:

 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)

Weight:

  

ioLogik E1210: 171 g  

 

ioLogik E1211: 187 g

 

ioLogik E1212: 171 g

 

ioLogik E1214: 177 g

 

ioLogik E1240: 179 g

Environmental Limits

Operating Temperature:

 -10 to 60°C (14 to 140°F)

Storage Temperature:

 -40 to 85°C (-40 to 185°F)

Ambient Relative Humidity:

 5 to 95% (non-condensing)

Regulatory Approvals 

EMI:

 FCC Part 15, CISPR (EN55022) class A

EMS:

 IEC 61000-4, IEC 61000-6

Shock:

 IEC 60068-2-27

Freefall:

 IEC 60068-2-32

Vibration:

 IEC 60068-2-6

Warranty

Warranty Period:

 2 years

Details:

 See www.moxa.com/warranty

Summary of Contents for ioLogik E1210

Page 1: ... Built in 2 port Ethernet switch for daisy chain topologies Free support of Moxa s push based Active OPC Server Lite Seamlessly connect to any SCADA system Save 80 on network bandwidth I O response that s seven times faster User defined Modbus TCP addressing MXIO programming library for Windows and WinCE VB VC NET and Linux C APIs Web configuration with Import Export function must be formed in a s...

Page 2: ...onnect to the next ioLogik in the daisy chain Applications such as factory automation security and surveillance systems and tunnel monitoring can make use of daisy chained Ethernet for building multi drop I O networks over standard Ethernet cables Many industrial automation users are familiar with the multi drop configuration typically used in fieldbus applications The daisy chain function on the ...

Page 3: ... O Test 2 I O Status ResponseTime This test used 128 ioLogik E2210 units with 2 560 I O points As shown in the figure the active architecture is 7 times better than the passive architecture in response time when the I O status changes Reduce Bandwidth Consumption by 80 Active Ethernet I O Passive Ethernet I O 0 1 2 3 4 5 0 1 2 3 4 5 6 7 7 Times Faster Active Ethernet I O Passive Ethernet I O archi...

Page 4: ... address table takes 100 seconds Active OPC Server To control an input or output channel of a remote Ethernet I O device running the most general Modbus TCP protocol requires specifying the Modbus address of those input and output channels This can take quite a bit of effort since you may need to look up the address and data type in the user s manual for address mapping and can also cause problems...

Page 5: ...ver current Limit 600 mA per channel Over temperature Shutdown 175 C typical 150 C min Output Current Rating Max 200 mA per channel Isolation 3K VDC or 2K Vrms Relay Output for ioLogik E1214 Type Form A N O relay outputs 5A Contact Rating 5 A 30 VDC 5 A 250 VAC 5 A 110 VAC Inductance Load 2 A Resistance Load 5 A Breakdown Voltage 500 VAC Relay On Off Time 1500 ms Max Initial Insulation Resistance ...

Page 6: ...NO 14 R2_C 15 R3_NO 16 R3_C 17 R4_NO 18 R4_C 19 R5_NO 20 R5_C 1 AI0 2 AI0 3 AI1 4 AI1 5 AI2 6 AI2 7 AI3 8 AI3 9 AI4 10 AI4 11 AI5 12 AI5 13 AI6 14 AI6 15 AI7 16 AI7 17 18 19 20 ioLogik E1214 top to bottom ioLogik E1240 top to bottom 1 COM0 2 DI0 3 DI1 4 DI2 5 DI3 6 GND 7 DI4 8 DI5 9 DI6 10 DI7 11 COM1 12 DIO0 13 DIO1 14 DIO2 15 DIO3 16 GND 17 DIO4 18 DIO5 19 DIO6 20 DIO7 ioLogik E1210 top to botto...

Reviews: