ioLogik 4000
Configuring I/O Modules
4-9
Thermocouple
To check the temperature status, click on the I/O module from the main page. The temperature will be shown
on the “I/O Status” tab.
To check the Modbus Address, click on the “Modbus Address” tab.
The thermocouple module supports different kinds of temperature sensor. To configure the sensor type, click
on
config
.
On this page, you can set up the sensor types and the temperature unit. Note that the configuration applies to
all channels on the same module. The related model is M-6201.
The
FilterType
represents the different sampling times. In Normal mode, the conversion time is about 200 ms.
In Enhanced mode, the conversion time will be about double, or around 400 ms. The thermocouple
temperature sensor is noise sensitive. Using Enhanced Mode can increase stability of the readings. CJC should
always be enabled.
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-11304-Moxa-NA-4010.aspx