- 6 -
STEP 2—
Mounting the EDS-P506E-4PoE Series on the
wall requires 4 screws. Use the EDS-P506E-4PoE
Series, with wall mount plates attached, as a guide to
mark the correct locations of the 4 screws. The heads
of the screws should be less than 6.0 mm in diameter,
and the shafts should be less than 3.5 mm in diameter,
as shown in the figure on at right.
NOTE
Before tightening the screws into the wall, make sure the screw
head and shank size are suitable by inserting the screw through
one of the keyhole-shaped apertures of the Wall Mounting Plates.
Do not screw the screws in all the way—leave about 2 mm to allow room
for sliding the wall mount panel between the wall and the screws.
STEP 3—
Once the screws are fixed
to the wall, insert the four screw
heads through the wide parts of the
keyhole-shaped apertures, and then
slide the EDS-P506E-4PoE
downwards, as indicated in the
figure at the right. Tighten the four
screws for more stability.
ATTENTION
The product should be mounted in an Industrial Control Panel and
the ambient temperature should not exceed 75°C.
Wiring Requirements
WARNING
Do not disconnect modules or wires unless power has been
switched off or the area is known to be non-hazardous. The
devices may only be connected to the supply voltage shown on
the type plate. The devices are designed for operation with a
Safety Extra-Low Voltage. Thus, they may only be connected to
the supply voltage connections and to the signal contact with the
Safety Extra-Low Voltages (SELV) in compliance with IEC950/
EN60950/ VDE0805.
ATTENTION
This unit is a built-in type. When the unit is installed in another
piece of equipment, the equipment enclosing the unit must
comply with fire enclosure regulation IEC 60950/EN60950 (or
similar regulation).