STEP 2:
Mounting the EDR-G9010 Series on the wall requires two M3
screws. Use the EDR-G9010 Series with the wall mount plates attached
as a guide to mark the correct location of the two screws. The wall-
mounting holes are marked
A
in the above diagram.
Wiring Requirements
WARNING
Do not disconnect modules or wires unless power has been
switched off or the area is known to be non-hazardous. The
devices may only be connected to the supply voltage shown on
the type plate. The devices are designed for operation with a
Safety Extra-Low Voltage. Thus, they may only be connected to
the supply voltage connections and to the signal contact with
the Safety Extra-Low Voltages (SELV) in compliance with
IEC 950/EN 60950-1/VDE 0805.
ATTENTION
This unit is a built-in type. When the unit is installed in another
piece of equipment, the equipment enclosing the unit must
comply with fire enclosure regulation IEC 60950-1/EN60950-1
(or similar regulation).