When Preset 1 is used to monitor a minimum value with setting “LE”, and Preset 2 is used to
monitor a maximum value with setting “GE”, then output 1 will operate with an
Automatic Startup-Inhibit, i.e. it will become enabled only after the measuring value has crossed
the minimum setting the first time.
Where no startup-Inhibit is desired, please use Preset 1 for Maximum and Preset 2 for Minimum
control.
6.4.5.
Response time of switching outputs
The response time of the transistor outputs is fully independent of the selected update time for
the display. With operating mode "Single" the response time of the outputs is typically
53 msec (provided that average filter and linearization function are switched off)
Use of the average filter and the linearization function will extend the response time of the
outputs correspondingly. When the fastest possible response of the outputs is important, please
make sure that these two functions are switched off.