background image

 

 

 Innovation in soft start technology

 

 

 
 
 

 

VMX-agility

TM

 

QUICK START GUIDE

 

 

MAN-AGY-014. Version 0 

 

 

 
 

Summary of Contents for VMX-agility

Page 1: ...Innovation in soft start technology VMX agilityTM QUICK START GUIDE MAN AGY 014 Version 0...

Page 2: ...ics UK deliverables including magnetic optical and or any other soft copy of these deliverables This document may not be reproduced in full or in part without written permission Enquiries about copyri...

Page 3: ...information contained in this manual is subject to change at any time and without prior notice In no event will responsibility or liability be accepted for direct indirect or consequential damages re...

Page 4: ...ovided if the heat output of the unit is greater than the cabinet will dissipate Theheat dissipated can be approximated with the formula Starting Watts agility start current A x start time s x number...

Page 5: ...us injury or damage to equipment Accessories The following accessories have been developed and tested for use with the agility range of soft starts VMX AGY 012 Remote keypad for VMX AGY 101 to VMX AGY...

Page 6: ...VMX AGY 101 to VMX AGY 113 Weight 1 97kg 3 75lb Fitting 25mm 0 98 25mm 0 98 75mm 2 95 75mm 2 95 25mm 0 98 Installation continued Air Flow inch Note VMX agility may be horizontally mounted with deratio...

Page 7: ...0 2019 Dimensions VMX AGY 201 to VMX AGY 205 Weight 6 kg 13 22LB VMX AGY 201 to VMX AGY 207 6 3 kg 13 89 VMX AGY 209 Fitting 25mm 0 98 100mm 3 93 100mm 3 93 Installation continued inch 40mm 1 57 40mm...

Page 8: ...AN AGY 014 Version 02 04 10 2019 Dimensions VMX AGY 301 to VMX AGY 305 Weight 15kg 33 10lb 125mm 4 92 Air Flow Installation continued 60mm 2 36 60mm 2 36 125mm 4 92 25mm 0 98 inch 13 1 332 2 4 60 6 4...

Page 9: ...be supplied as an option for short circuit protection of the semiconductors These fuses must be fitted externally to the VMX agilityTM chassis to comply with certain standards It is the responsibility...

Page 10: ...lectrical Connections Mains Circuit Wiring Diagram Electrical Installation continued 3 Phase Electrical Supply Connections L1 L2 L3 RJ45 connector Modbus RTU USB Connector Control Terminals AC Inducti...

Page 11: ...Gear Provided by customer L N PE Single Phase Operation VMX agilityTM soft starts may be operated with a single phase supply and motor The base rating of the unit is unchanged Electrical Connection E...

Page 12: ...ed 24Vdc 3 250Vac 2A Cos 0 5 Digital Input 2 D2 Selectable Functions Different functions may be assigned to Digital Input 2 in the I O menu Available assignments are Reset Hold Start Ramp Enable Fire...

Page 13: ...dc Note 110 230V control supply possible with optional control supply module VMX AGY 021 or VMX AGY 020 for models VMX AGY 101 to VMX AGY 113 only K1 0V K2 2 24V D1 D2 13 0V COM 14 21 22 FU1 24V dc No...

Page 14: ...rmined by the Motor Current setting and the Trip Class setting Trip class choices are Class 10 Class 20 and Class 30 The VMX agilityTM soft starters are protected using full I 2 T motor overload with...

Page 15: ...e A flashing centre button indicates that a menu item may be selected or saved Configuration and Parameters Status messages Instantaneous motor current Control scheme Local Control terminal Modbus RTU...

Page 16: ...Quick Start Guide MAN AGY 014 Version 02 04 10 2019 Operation Local Motor Start Example Navigation Method Auto Application Setup Configuration and Parameters continued Quick Return to Status Screen Ce...

Page 17: ...High Inertia 40 10 0 30 3 5 60 Fan Low Inertia 30 15 0 10 3 5 30 Grinder 40 10 0 20 3 5 40 Mill 40 10 0 20 3 5 40 Mixer 10 10 0 20 4 25 Moulding M C 10 10 0 10 4 5 25 Press Flywheel 40 10 0 20 3 5 40...

Page 18: ...pply Number of poles 3 main poles 2 main poles controlled by semiconductor switching element Rated insulation voltage Ui Main circuit See Key to part numbers Control supply circuit 230Vac r m s 1 Rate...

Page 19: ...frequency dc Rated voltage Uc 24Vdc With VMX AGY 020 VMX AGY 021 module Control Supply Supply input L N Kind of current rated frequency ac 50 60Hz 5Hz Rated voltage Us 110V to 230Vac Rated input curr...

Page 20: ...applies when the finger guards as supplied are fitted 7 Transient surge suppression shall be installed on the line side of this equipment and shall be rated 600_V phase to phase suitable for overvolt...

Page 21: ...UL508 Table 6 4 and UL508A Table 15 1 Environmental Specifications Model VMX AGY 101 103 105 107 109 111 113 Frame Size 1 Heat output W 9 12 14 16 20 25 30 Weight kg lb 1 97 4 20 Model VMX AGY 201 203...

Page 22: ...elay Fuses with a Maximum Rating of ___Z1___ or by a Circuit Breaker with a Maximum Rating of ___Z2___ 2 Correctly selected semiconductor fuses can provide additional protection against damage to the...

Page 23: ...100 250 300 VMX AGY 303 VMX AGY 305 361 110 200 250 361 125 125 150 300 350 VMX AGY 305 Rating Table Horizontally Mounted Ie kW 1 FLA Hp 2 Trip Class 10 Trip Class 20 Trip Class 30 A 3 230V 400V 500V...

Page 24: ...toka Spodaj opisana dela smejo izvajati samo elektrostrokovnjaki in elektrotehni no pou ene osebe Nebezpe enstvo ohrozenia ivota elektrick m pr dom Pr ce ktor s ni ie op san sm vykon vat iba elektroo...

Reviews: