04. TROUBLESHOOTING

INSTRUCTIONS FOR FINAL CONSUMERS AND SPECIALIZED TECHNICIANS

Anomaly

Procedure

Behavior

Procedure II

Discovering the origin of the problem

• Pillar doesn’t 

work.

• Check that the 

control board has 

power and it is 

working correctly.

• Still not working.

• Consult a qualified 

technician.

• Pillar doesn’t 

move but 

makes noise. 

• Unlock the pillar 

and move it manually 

to check if there 

are mechanical 

problems.

• The pillar is stuck.

• Consult a technician.

• The pillar moves 

easily.

• Consult a qualified 

technician.

• Pillar opens 

but doesn’t 

close.

• Unlock the pillar 

and manually move 

it to the closed 

position.

Lock the Pillar (s) 

again.

Turn the general 

electrical board off 

for 5 seconds, then 

turn it back on. Give 

opening order with 

the remote control.

• Pillar opened but 

didn’t close again.

• Check if there 

are any obstacles 

obstructing the 

movement of the pillar.

• Check if any control 

devices of the pillar 

are stuck and sending 

a permanent signal to 

the control board.

• Consult a qualified 

technician.

• Pillar doesn’t 

make complete 

route.

• Unlock the pillar 

and move it manually 

to check if there 

are mechanical 

problems.

• Encountered 

problems?

• Consult an 

experienced pillars 

expert.

• The pillar moves 

easily?

• Consult a qualified 

technician.

• Open control box and check if it 

has 230V power supply;

• Check input fuses of the control 

board;

• Disconnect pillars from control 

board and test them by

connecting directly to power 

supply.

 

• If the pillar work, the problem 

is on the control board.

Pull it out and send it to our 

technical services for diagnosis;

• If the pillar don’t work, remove 

them from installation site and 

send to our technical services for 

diagnosis.

1 • Disconnect the pillar from control 

board and it them by connecting 

directly to power supply in order to 

find out if it has problems;

All control boards have LEDs that 

easily allow to conclude which 

devices are with anomalies. 

All safety devices LEDs (DS) in 

normal situations remain On. 

All "START" circuits LEDs in normal 

situations remain Off. 

If LEDs devices are not all On, 

there is some security systems 

malfunction (photocells, safety 

edges). 

If "START" circuits LEDs are turn 

(Op and Cl), there is a control 

device sending permanent signal.

3 • If the pillar work, the problem is 

on the control board.

Pull it out and send it to our 

technical services for diagnosis;

A) SECURITY SYSTEMS:

• Close with a shunt all safety 

systems on the control board 

(check manual of the control board 

in question). If the automated 

system starts working normally 

check for the problematic device.

 

• Remove one shunt at a time 

until you find the malfunction 

device.

• Replace it for a functional 

device and check if the motor 

works correctly with all the other 

devices. If you find another one 

4 • If the pillar don’t work, remove 

them from installation site and 

send to our technical services for 

diagnosis.

defective, follow the same steps 

until you find all the problems.

B) START SYSTEMS:

• Disconnect all wires connected 

to the START connector. 

• If the LED turned OFF, try 

reconnecting one device at a time 

until you find the defective device.

NOTE 

• In case procedures 

described in sections A) and B) 

don’t result, remove control board 

and send to our technical services 

for diagnosis.

• Disconnect motor from control 

board and test it by connecting 

directly to power supply in order 

to find out if it is broken; 

• If the pillar(s) doesn’t work, 

remove it from installation site and 

send to our technical services for 

diagnosis.

3

 • If motor work well and move 

the pillar at full force during the 

entire course, the problem is from 

controller. Set force using trimmer 

on the board. Make a new working 

time programming, giving suffient 

time for opening and closing with 

appropriate force (consult control 

board manual).

4

 • If this doesn’t work, remove 

control board and send it to 

technical services.

NOTE 

• Setting force of the 

controller should be suficiente to 

make the pillar open and close 

without stopping, but should stop 

and invert with a little effort from 

a person. In case of safety systems 

failure, the gate shall never cause 

physical damaged to obstacles 

(vehicles, people, etc.).

Check all motion systems related 

with the pillar and to find out what 

is the problem.

 Check all motion systems related 

with the pillar and to find out what 

is the problem.

Summary of Contents for MPIE10

Page 1: ...v1 0 REV 03 2021 MPIE10 MPIE10 EN INSTALLER AND USER S MANUAL...

Page 2: ...erial controls etc should not be disposed of as other household waste at the end of its useful life To avoid possible harm to the environment or human health resulting from the uncontrolled disposal o...

Page 3: ...persons with experienced in terms of usage of the product in a safe manner and who understands the risks and dangers involved Children shouldn t play with the product or opening devices to avoid the...

Page 4: ...an emergency Ifthesystemrequiresanyrepairormodification unlocktheautomatism turn off the power and do not use it until all safety conditions have been met In the event of tripping of circuits breakers...

Page 5: ...ight 35Kg 40Kg 45Kg Power Supply 24 Vdc Power 150W Nominal power consumption 3A Operating Temperature 20 C 50 C Material of the moving piece 2 5mm Stainless steel Cover Non slip 4mm Stainless steel Ma...

Page 6: ...Dimension c 370mm 570mm 785mm 03 INSTALLATION AUTOMATISM INSTALLATION CREATE FOUNDATION Drill a hole on the ground with the necessary dimension for the placement of the pillar taking into account the...

Page 7: ...E AUTOMATISM INSTALLATION At the base of the pillar place a tube for draining waste water with a minimum inclination of 10 Provide a tube to pass the electric cable to the control board Place sand aro...

Page 8: ...On there is some security systems malfunction photocells safety edges If START circuits LEDs are turn Op and Cl there is a control device sending permanent signal 3 If the pillar work the problem is o...