16

- insufficient pressure of the water  in the hydraulic core circuit (irregularity)

- Absence of draft on start (irregularity):

The boiler shutting-down in safety conditions.

The pressure visualizing

:

in case the pressure sensor measures an insufficient pressure of the water in the system, (<0,5
bar) the burner and the pump are deactivated and  the flickering  intermittent symbol  Err E1
occurs on the display.
Disturbance of a temperature sensor (irregularity):
1.Sensor for the central heating water: any disturbance of the sensor caused by a wrong
contact or a short-circuit leads to the immediate deactivation of the burner, pump and the
flickering intermittent symbol Err E1 occurs.
2.Sensor for DHW: any disturbance of the sensor caused by the wrong contact doesn`t lead to
the immediate deactivation of the burner but to displaying the flickering intermittent symbol Err
E4 for monothermal boilers.

In case the pressure switch doesn`t commute the

TW pre-cleaning in due time, the boiler won`t start running and the intermittent symbol Err E5
will occur after 10 seconds. This irregularity vanishes when the flame is detected at the end of
the operating cycle.
-Removing the combustion products causes the activation of the safety devices (irregularity):
OPEN CHAMBER

The safety devices of the combustion products are activated and cause the boiler automatic

shutting down, the intermittent symbol E5 occurs on display. This irregularity disappears only
pressing the button SW3. In case the limit thermostat (LT) is activated, the system will shut
down automatically and the intermittent symbol Err E8 occurs on the control panel display. This
irregularity persists even if LT is deactivated. To reset the normal operating system it is sufficient
to press the reset button SW2.

In case the final user establishes that the appliance has an abnormal running, if the error codes
keep displaying or if the appliance manifestations can not be understood, he has the obligation
of shutting-down the boiler as soon as possible and in maximum safety conditions. The user
must perform the following operations:
* press STAND BY and the boiler shuts down
* disconnect the boiler from  the electric power supply circuit  by unplugging
* Disconnect the gas supply circuit by switching on the gas valves
* Interrupt the DHW and the DCW circulation by switching on the gas valves corresponding to
these circuits.
After boiler shutting down in maximum safety conditions, the user will call the service unit he
belongs to (see chapter 1, subchapter 1.4).

The pressure from installation is displayed and it is useful to installation filling up. The
beneficiary will check recurrently whether the pressure in installation has lowered below the
value set on filling.
The pressure will maintain between 1-2 bars. If the minimum pressure lowers below the value of
0,5 bars the boiler will display the E1 signal and it will shut down.  If the pressure exceeds the
value of 3 bars, the safety relief valve will open and it will release the system from the
accumulated pressure.

Summary of Contents for C15SPV 24MEFM

Page 1: ...lexandru cel Bun Neamt District Postal Code 617511 Romania Phone 40 233 24 17 46 233 24 19 33 Fax 40 233 24 19 29 E mail www motan ro office vaduri kober ro TECHNICAL INSTRUCTIONS FOR INSTALLATION USA...

Page 2: ...ditional facilities that may be obtained by Handing over to the beneficiary Recommendations for the yearly checking Marking documents packing storage transport quality and warranty conditions Marking...

Page 3: ...tope interior ceramics fibre lined is designed to allow the transfer to the exchanger with less heat leakages In case of the CH circuit of the two heat exchangers type the heat resulted from fuel gas...

Page 4: ...o be consulted by the new user installer In case of some components damaging there will be used only the original components You must have the manufacturer s acceptance to use some components from ano...

Page 5: ...ption Weight Heat exchanger output 0 5 i 3 bar 40 80 C 3 4 1 2 3 4 275 415 700 850 7 L Central heating Minimum and maximum admitted pressure Temperature on the heating circuit Connections inlet outlet...

Page 6: ...the copper pipe 14x1 is stainless made forced or atmospherics with 11 cannular inclines and it runs with fuel gas NG or LPG The burner output is set in a modulated system by means of a gas modulating...

Page 7: ...line the relief valve of the circuit is designed to reduce the pressure from the heating circuit and to open at 3 bars full pressure the ventilation circuit of the installation is made of an air rele...

Page 8: ...er of the boiler running see the attached drawing the measuring and pilot cells of the functional parameters for the boiler which sends the temperature signal to the electronic control block of the he...

Page 9: ...stallation we must be aware of the hydraulic features of the pump 9 The hydraulic characteristic of the pump Pressure pump P mca Pump output Q mc h the third stage of the speed the second stage of the...

Page 10: ...nstalling activities It is important to pay attention to the pipes dimensions head losses and heating elements while designing the heating system The installation filling up must be done with softened...

Page 11: ...low two operations The setting from the electronic board which is performed by positioning the J6 jumper see the Electrical Diagram on the two pines LPG module The J6 jumper is situated on a single pi...

Page 12: ...o the current standards The technical instructions should be studied before mounting installing starting or servicing It s forbbiden to install the boiler without earthing THE COUPLING FOR SCAVENGING...

Page 13: ...ostat may be installed on demand UTILIZATION INSTRUCTIONS The control board Display board LCD in the user module SW8 SW 7 SW2 Button Operation function This button shuts down opens out the boiler the...

Page 14: ...tting will decrease While visualizing the set point by the heating the symbol 7 is flickering DHW Pressing the button once the preset temperature of the DHW is displayed if you keep pressing the setti...

Page 15: ...ing Symbol 13 inermitent the conthrol system of boiler is achieving the mentain of temperature in the primary circuit as so at the request of DHW the time necessary for reaching the setted temperature...

Page 16: ...s irregularity disappears only pressing the button SW3 In case the limit thermostat LT is activated the system will shut down automatically and the intermittent symbol Err E8 occurs on the control pan...

Page 17: ...in case due to some disturbances the water temperature from the boiler will be below zero degree for more than 2 3 hours the boiler the heating installation and the domestic water installation will b...

Page 18: ...mmended temperature C 90 80 70 60 50 40 30 20 10 0 40 20 0 20 40 Outdoor temperature C Recommended temperature C T amb 30 C Ke 35 Ke 5 T amb 10 C The heating circuit temperature diagram depending on t...

Page 19: ...signed by the authorized person too who performs the putting into service who trained The person who performs the starting has the right of refusing the putting into service of the boiler if he estab...

Page 20: ...on and setting by the authorized personnel The yearly examinations are achieved on beneficiary demand and at the expense of the beneficiary the first year examination is compulsory to maintain the gua...

Page 21: ...ere is no flame Defective Defective Defective The component Temperature sensors The gas valve The heat exchanger Ignition ionization electrode Parasite spark Replace the ignition ionisation electrode...

Page 22: ...s lay out is through a below 0 C area and it froze there is air in installation E2 E2 The user calls the authorized service unit he belongs to The user calls the authorized service unit he belongs to...

Page 23: ...s boiler with forced draft MAXOPTIMUS C15SPV24MEFM THE Coupling 1 DHW inlet CH turn DHW gas supply cold water CH return 2 DHW outlet 3 Central heating turn 4 Central heating return 5 Gas supply 1 2 1...

Page 24: ...zation electrode 5 electrical pump with exhauster 6 burner 7 gas modulator 8 3 bar safety valve 9 filling valve 10 flowmeter for the sanitary circuit 11 automatic by pass 12 3 way valve 13 temperature...

Page 25: ...ings diagram for the wall hung gas boiler with forced draft OPTIMUS MT C15 SPV 24 MEFM Plan 3 25 1 2 700 65 51 64 65 A B C D E 3 4 3 4 3 4 1 2 1 2 415 226 189 Panta 3 aprox 2 134 75 280 Gaz Apa 125 15...

Page 26: ...ical flue system applications for the wall hung gas boiler with forced draft C15SPV24MEFM 26 C12 C12x C12 C12x C82 C32 C32x C42 C22 C22 COAXIAL FLUE TWIN FLUE Lmin 1m Lmax 3m Lmin 1m Lmax 5m Lmin 1m L...

Page 27: ...TR 2 EARTH FLAME ELECTRODE FAN JP 1 CH PROBE DHW PROBE EXT PROBE FLOWMETER RRESSURE TRANSDUCER MODULATOR COIL CRONO TERMOSTAT OPEN THERM 961 INTERFACE APS GND VCC GAS VALVE HALL SENSOR SAFETY THERMOS...

Reviews: