4.0 ALARM MESSAGES
The alarms are displayed by means of messages. In case of
alarm consult your Generating Set manufacturer. To remove
the message, turn OFF the KEY-SWITCH. The EP6 may show
one of the following:
(1) [FUEL]
This message indicates Low Fuel in the tank .
The engine stops if the contacts remain closed for 5 minutes
continuously.
(2)
To determine the value that caused the failure, push the
[F1] pushbutton.
4.1 OPERATING messages
EP6 features messages to inform you about the following:
[uuuu]
Glow-plugs timing
[U— ]
Voltage out of range
[StA-]
Start prompt
[. . . .]
Starting by key switch
[rESt]
Rest timing
[tESt]
Automatic Test
[CAL]
Calibration
[ProG]
Programming
[StOP]
Stopping cycle
5.0 LEDS FOR VISUAL INDICATION
The EP6 features two LEDs
(see section 10.0)
to indicate the
following conditions:
[ENGINE RUNNING]
: this green led illuminates when the
engine is running.
[AUTO]
:
this yellow LED blinks to indicate a standby mode. The
EP6 monitors the REMOTE CONTROL and expects a com-
mand. The LED illuminates continuously when the REMOTE
START is activated.
5.1 LEDS AND DISPLAY TEST
A test of the LEDs and DISPLAY is obtained automatically
anytime the key switch is turned ON. The LEDs and DISPLAY
light up for about 1 second.
6.0 PARAMETERS AND SETTINGS
The unit is programmed by the supplier of the Generating Set.
Contact the Generator manufacturer in order to have the per-
mission to program the module. It is possible to read the status
of the internal programming at anytime. Follow the instructions:
A) Turn the Key in OFF (if the display indicates [STOP], wait
until it disappears)
B)
Push the pushbutton [F1] the display will show the first
programmable parameter
[P.0]
.
C) Push the pushbutton [F1] the display will indicate the value
of the parameter ([ 1"]).
D) Push the pushbutton [UP-DOWN] to select a parameter.
Push [F1] to display the setting.
E) The display returns to menu mode if you have not used the
pushbuttons for 2 minutes.
The list of the parameters follows ([ ' ] means minutes and
[ '' ] means seconds). Some parameters may differ accord-
ing to the programming done by the genset manufacturer.
[OIL]
Low Oil Pressure
[ °C ]
High Temperature
[O.SPd.]
Over Speed of the engine
[U.SPd]
Under Speed of the engine
[bELt]
Failure of the belt
[ALAr]
External Emergency Stop
[FUEL](1)
Low Fuel in the tank
[FAIL]
Starting Failure Alarm
[E 04]
Alternator Failure
[E 05](2)
Generator Overload
[Hi H](2)
Generator Over Frequency
[Lo H](2)
Generator Under Frequency
[Hi U] (2)
Generator Under Voltage
[Lo U](2)
Generator Under Voltage
[XX.X]
Battery Voltage
[Err ]
Memory error
M
39.12.1
ENGINE PROTECTION
EP6
REV