21/01/08 25460-GB
Technical data
GE 4500 HBS
GE 4500 HBS-AVR
M
1.5
REV.2-05/12
Technical data
GE 4500 HBS / GE 4500 HBS-AVR
GENERATOR
*Stand-by single-phase power
4.9 kVA (4.4 kW) / 230 V / 21.3 A
*
PRP single-phase power
4 kVA (3.6 kW) / 230 V / 17.4 A
Frequency
50 Hz
Cos
ϕ
0.9
* Output powers according to ISO 8528-1
ALTERNATOR
self-excited, self-regulated, brushless
(With brush - AVR Vers)
Type
synchronous, single-phase
Insulating class
H
ENGINE
Mark / Model
HONDA / GX 270
Type / Cooling system
Petrol 4-Stroke OHV/ Air
Cylinders / Displacement
1 / 270 cm
3
*
Stand-by net power
5.7 kW (7.7 HP)
*
PRP net power
4.6 kW (6.2 HP)
Speed
3000 rpm
Fuel consumption
(75% of PRP)
1.6 l/h
Engine oil capacity
1.1 l
Starter
recoil
* Powers according to SAE J1349
GENERAL SPECIFICATION
Tank capacity
5.3 l
Running time
(75% of PRP)
3.3 h
Protection
IP 23
Dimensions / max. Lxwxh (mm) *
785x440x490
Weight (dry) *
56 Kg
Measured acoustic power LwA (pressure LpA)
96 dB(A) (71 dB(A) @ 7 m)
Guaranteed acoustic power LwA (pressure LpA)
97 dB(A) (72 dB(A) @ 7 m)
* Dimensions and weight are inclusive of all parts.
2000 / 14 / CE
OUTPUT
Declared power according to ISO 8528-1 (temperature 25°C, 30% relative hummidity, altitude 100 m above sea level).
(*Stand-by) = maximum available power for use at variable loads for a yearly number of hours limited at 500 h. No overload is
admitted.
(**Prime power P.R.P.) = maximum available power for use at variable loads for a yearly illimited number of hours. The average
power to be taken during a period of 24 h must not be over 80% of the P.R.P.
It’s admitted overload of 10% each hour every 12 h.
In an
approximative
way one reduces: of 1% every 100 m altitude and of 2.5% for every 5°C above 25°C.
ACOUSTIC POWER LEVEL
ATTENTION:
The concrete risk due to the machine depends on the conditions in which it is used. Therefore, it is up to the end-
user and under his direct responsibility to make a correct evaluation of the same risk and to adopt specific precautions (for
instance, adopting a I.P.D. -Individual Protection Device)
Acoustic Noise Level
(L
WA
)
- Measure Unit dB(A):
it stands for acoustic noise released in a certain delay of time. This is not
submitted to the distance of measurement.
Acoustic Pressure (Lp)
- Measure Unit dB(A):
it measures the pressure originated by sound waves emission. Its value changes
in proportion to the distance of measurement.
The here below table shows examples of acoustic pressure (Lp) at different distances from a machine with Acoustic Noise Level
(
L
WA
)
of 95 dB(A)
Lp a 1 meter = 95 dB(A) - 8 dB(A) = 87 dB(A)
Lp a 7 meters = 95 dB(A) - 25 dB(A) = 70 dB(A)
Lp a 4 meters = 95 dB(A) - 20 dB(A) = 75 dB(A)
Lp a 10 meters = 95 dB(A) - 28 dB(A) = 67 dB(A)
PLEASE NOTE:
the symbol when with acoustic noise values, indicates that the device respects noise emission limits
according to 2000/14/CE directive.
2000 / 14 / CE