6
Morrison Bros. Co. ‑ Dubuque, IA ‑ 800‑553‑4840
918AC‑0160 PP
Rev. 09-27-2022
DIP Switch Configuration Tables
Input Module
Table 1 Expansion board SW1 – Non-Persistent Output
Position
Setting
ON
This output channel relay will be
reset to its normal condition when
the alarm has been acknowledged
OFF
The alarm acknowledgement
has no effect on this output
1
Channel 1
Channel 1
2
Channel 2
Channel 2
3
Channel 3
Channel 3
4
Channel 4
Channel 4
Table 2 Expansion board SW2 – Output Auto-Timeout
Position
Setting
ON
This output channel relay will be
reset to its normal condition when
the auto‑timeout timer has expired
OFF
The auto‑timeout timer has no
effect on this output
1
Channel 1
Channel 1
2
Channel 2
Channel 2
3
Channel 3
Channel 3
4
Channel 4
Channel 4
Table 3 Expansion board SW4 – Output Timeout Value
Position
Setting
Relay Output Auto-Timeout
0
3 minutes
1
6 minutes
2
9 minutes
3
12 minutes
4
15 minutes
5
18 minutes
6
21 minutes
7
24 minutes
8
27 minutes
9
30 minutes