background image

3

Morrison Bros. Co.  ‑  Dubuque, IA  ‑  800‑553‑4840

918AC‑0160 PP

Rev. 09-27-2022

Auto-Timeout Output Function

The Auto-Timeout relay output function allows each relay output to be reset to its normal condition after a 

configurable amount of time. The Timeout value can be adjusted in 3 minute increments from 3 to 30 minutes 

using the rotary switch. The timeout value is calculated using the following formula:

Timeout (minutes) 

= (

+ 1) 

x

 3

The value of 

n

 in the formula is set using the rotary switch. For example, a value of 0 will set the Auto-Timeout 

to 3 minutes and a value of 2 will set the Auto-Timeout to 9 minutes.

NOTE: 

The Auto-Timeout function can be used with the Non-Persistent function (see page 2). However, the 

relay output Latching Mode (see page 4) takes precedence over the Auto-Timeout function. 

Figure 3 -  Auto-Timeout Relay Output Configuration

1. Locate the rotary switch, Timeout Value, SW 4, on the expansion board mezzanine (see Figure 3).

2. Use a small screwdriver to turn the rotary dial to the desired auto-timeout value. A value of “0” corresponds 

to a 3 minute timeout value. The timeout value will start at 3 minutes (position “0” of the dial) and increase 

by 3 minutes for each count of the rotary dial, up to the maximum timeout of 30 minutes (position “9” of the 

dial).

NOTE:

 The auto-timeout value is applied to all outputs with the auto-timeout setting enabled. Different values 

cannot be set for individual outputs. 

3. Locate the four position, Auto-Timeout switch, SW 2 on the Motherboard (see Figure 3).

4. Place the DIP switch Position One in the “ON” position to configure the Motherboard to reset the channel 

1 relay output when the auto-timeout timer has expired. Place the DIP switch Position One in the “OFF” 

position to prevent the auto-timeout timer from changing the state of the channel 1 relay output.

Summary of Contents for 918AC Series

Page 1: ...cendie ou d explosion des blessures graves ou la mort Contents Installation 1 Steps to Configure the 918AC Series System Interface Motherboard 2 Non Persist Output Function 2 Auto Timeout Output Funct...

Page 2: ...elay output when the triggering alarm condition s have been acknowledged Place the DIP switch Position One in the OFF position to prevent the alarm acknowledgement from changing the state of the chann...

Page 3: ...re 3 Auto Timeout Relay Output Configuration 1 Locate the rotary switch Timeout Value SW 4 on the expansion board mezzanine see Figure 3 2 Use a small screwdriver to turn the rotary dial to the desire...

Page 4: ...the auto timeout timer has expired Place the DIP switch Position Four in the OFF position to prevent the auto timeout timer from changing the state of the channel 4 relay output 8 Locate the reset pu...

Page 5: ...and configure the channel 4 input as the reset condition place DIP switch Position One and Two the ON positions 3 Use DIP switch Positions Three and Four to set the Latching Mode for the channel 2 rel...

Page 6: ...nel 2 3 Channel 3 Channel 3 4 Channel 4 Channel 4 Table 2 Expansion board SW2 Output Auto Timeout Position Setting ON This output channel relay will be reset to its normal condition when the auto time...

Page 7: ...OFF Channel 1 Latching Mode Enabled Input 2 Reset OFF ON Channel 1 Latching Mode Enabled Input 3 Reset ON ON Channel 1 Latching Mode Enabled Input 4 Reset Position Setting 3 4 OFF OFF Channel 2 Latch...

Reviews: