Description of functioning
t e c h n i c a l
P
38
Failures and
Fault
Finding:
The different type of failures the boiler will show with a
lockout light
:
F01
The boiler try
s
3 times to
establish
the fl ame:
each sequence lasts
6 second
s
between
each sequence the stop time is 5 seconds
If the ionisation
electrode fails to detect a flame
the boiler will lock out (F1)
locked.
When the boiler is working
and
the fl ame
fails due to a malfunction of the gas valve
or ionisation electrode
after 1 second without fl ame
detection the boiler will shut down
(gas valves)
The boiler will then attempt to relight if no flame is detected the boiler will
lock out (F1)
lapoouuuuuuuuuuuuuuuuuuuuufdfd
no oiuuuuuuuuuuuuuuAC ppppp
POSSIBLE CAUSES
-NO GAS
-NO SPARK
- FAULTY GAS VALVE
- FAULTY IONISATION ELECTRODE
- FAULTY PCB
32