Flexible Sensors for Thermowell 

Temperature Assemblies

Page 2

Installs in Minutes

 

Each of the three installation options uses different 

parts from the installation kit; expect to have parts left 

over after installation.  Read through all steps for the 

enclosure type prior to beginning installation. 

 

 

Figure 2.  The WORM Kit Components

Sensor Probe & Wiring

2-Inch & 1-Inch Spacers–

keeps the WORM straight 

inside the lag

Spring–

for pushing the sensor probe

against the base of the thermowell

Stopper–

for use in 

Generic Installations,
holds the WORM assembly 
inside of the thermowell

Cap–

for use in Head-Mount and Field Enclosure

Installations, holds the WORM assembly inside of the 
thermowell assembly

Clip–

in Field Enclosure

Installations, holds the 
cap in place

Field Enclosure Installation 

 

(Including Moore Industries’ DH & BH enclosures)

 

Installation Components Required:  

Sensor Probe, 

Spring, Cap, Clip, and Spacer(s).

 

1. 

 Determine the length of the thermowell assembly (see 

the illustration to the right).  Cut the WORM Spring to be 

between 1 and 1½ inches 

longer

 than the length of the 

assembly (this is necessary so that the Spring's 

compression securely holds the sensor probe to the 

bottom of the thermowell).  

2. 

 Ensuring that the uncut portion of the Spring faces down 

towards the Sensor Probe, slide the Spring over the sensor 

wires and onto the end of the Sensor Probe.

3. 

 Snap the Clip onto the Cap.  Then slide the Cap/Clip 

combination over the sensor wires onto the top of the 

Spring. 

 

 

4. 

 Remove the instrument from the enclosure (if 

necessary).  Insert the WORM sensor into the thermowell.  

Slide the appropriate length(s) and number of Spacers 

to keep the WORM Spring straight inside the thermowell 

assembly lag (Spacers may not be required).

 

5.  

Using pliers, grasp the Cap/Clip combination by the 

niche at the top of the Cap, and insert it into the 

 

enclosure’s sensor entry port to compress the WORM 

Spring into the thermowell.  Reinstall the instrument into 

the enclosure.  Connect the sensor wires.

Sensor

Probe

1-Inch

Spacer

Spring

Cap 

& Clip

Field Enclosure

(Including Moore Industries’ DH & BH)

2-Inch

Spacer

1-Inch

Spacer

Determine the 

length of the 

thermowell

assembly and 

cut the Spring

to be between

1 and 1½ 

inches longer.