Mooney Flowgrid Installation, Operation & Maintenance Manual Download Page 6

6  

|

  Dresser

 Installation

WARNING

 

1. PERSONNEL:

 Installation of the Flowgrid

®

 valve/ 

regulator should be made by qualified personnel familiar 
with high pressure piping and pilot operated regulators.

 2.   PRIOR INSPECTION:

 Inspect the main valve, pilot, 

and tubing for any damage that might have occurred in 
shipping. Make sure the body, pilot lines, and inlet piping 
are clear and free from foreign material. 

3.   ORIENTATION:

 The Flowgrid

®

 valve may be installed 

in any position - the best position being one that 
provides easiest access for pilot adjustment and valve 
maintenance.

4.   SCREWED END VALVES:

 Apply pipe compound to the 

male threads starting one or two threads back from the 
end prior to assembling the joint.

5.   FLANGED END VALVES:

 Use suitable line gaskets and 

good bolting practices with flanged bodies. A crisscross 
pattern of incrementally tightening the line bolts is 
recommended.

6.   WELD END BODIES:

 Remove the Spring Case and 

all trim parts including diaphragm and O-rings before 
welding a buttweld and/or a socket weld end Flowgrid

®

 

valve. Electric arc welding is recommended to minimize 
heat build-up on the body assembly. Reassemble valve 
(refer to the MAINTENANCE section of this manual for 
Disassembly and Assembly procedures) and pressurize 
with air to check for leaks prior to putting the valve in 
service.

 Personal injury, equipment damage, or leakage due to 
explosion of accumulated gas or bursting of pressure 
containing parts may result if this valve/ regulator is 
overpressured or is installed where service conditions 
could exceed the limits given in the specification of 
this manual or on the nameplate, or where conditions 
exceed any ratings of the adjacent piping or piping 
connections. Verify the limitations of both valve and pilot 
to ensure neither device is overpressured. To avoid such 
injury or damage, provide pressure relieving or pressure 
limiting devices (as required by Title 49, Part 192, of the 
U.S. code of Federal Regulations, by the National Fire 
Codes of the National Fire Protection Association, or 
applicable codes) to prevent service conditions from 
exceeding those limits. Additionally, physical damage 
to the valve/regulator could break the pilot off the 
main valve, causing personal injury and/or property 
damage due to explosion of accumulated gas. To avoid 
such injury and damage, install the regulator in a safe 
location.

WARNING

 Gas Regulators installed in confined or enclosed spaces 
should be provided with adequate ventilation to prevent 
the possibility of gas buildup or accumulation from 
leaks and venting.  Leaks or vented gas may accumulate 
causing personal injury, death, or property damage.  
Pilot spring cases and the regulator enclosure should 
be vented to a safe area away from air intakes, or any 
hazardous location.  The vent lines and stacks must be 
protected against condensation and clogging.

 7.   PILOT SUPPLY LINES:

 Run a 3/8-inch or 1/2-inch pilot 

supply line from the valve body connection on the inlet 
side of the Flowgrid

®

 valve to the pilot supply Filter or 

directly to the pilot Restrictor.

NOTE: A shutoff valve is not required in the supply to the 
pilot, but if one is installed it should be a full opening ball 
valve type. 

8.   A TYPE 30 FILTER 

in the pilot supply line is recom-

mended to clean dirt and other particulates that could 
affect the restrictor or variable orifice in the pilot.  Use 
a 1/4” nipple to mount the filter to the body tap on the 
Flowgrid

®

 valve.

9.   FILTER OUTLET:

 Run 3/8 inch tubing or 1/4- inch 

pipe from the filter OUTLET port to the INLET side of the 
restrictor in the pilot system of the regulator. The TYPE 
30/30A/30S FILTER has two OUTLET ports for ease of 
tubing. Block the other port with the plug provided or 
mount a gage to monitor inlet pressure if desired. 

NOTE: To avoid galling when stainless steel to stainless 
steel connections are made use a lubricant (such as 
NEVER SEEZ by Bostik). For best results Lightly lubri-
cate the female threads. Mixing the lubricant with pipe 
dope is also acceptable. Do not exceed more than 1/4 
turn past the point the threads start to bind.

10.  PILOT GAS HEATERS (OPTIONAL):

 Pilot supply gas 

can be heated to prevent the formation of ice or hydrates 
in the pilot system. Pilot supply gas heaters should be 
connected after the pilot filter (if one is used). Do not 
directly heat to entire Flowgrid

®

 valve to prevent freezing; 

internal rubber components can be heated beyond their 
max temperature rating causing potential damage. 

11.  CONTROL LINES: 

Control lines should be run from 

the pilot mounted on the Flowgrid

®

 valve to a point 8 to 

10 pipe diameters away from the valve (Refer to Piping 
Schematics). Use Table 4 as a guide for the ideal tubing 
to use. Reduce as necessary to connect to the pilot.

Outlet Pressure

Pilot Regulator 
with:

Inches W.C. to 
2 psi

2 psi to 5 psi

5 psi & above

Static Sense 
Line (No 
Flow)*

1/2” Pipe 
minimum

1/2” Tubing

3/8” Tubing

Sense Line 
with Flow*

3/4” to 1” 
Pipe

1/2” Pipe

1/2” Tubing

 *The Flowgrid

®

 Series 20 Pilot has a static sense line.

Summary of Contents for Flowgrid

Page 1: ...y or redundancy Non stretching fabric reinforced diaphragm for stability and fast response at all temperatures Positive spring shutoff Two stage pressure drop to minimize noise and provide cavitation...

Page 2: ...ng spring case Table 1 Table 2 Figure 1 The throttle plate 2 supports the diaphragm and provides a machined surface that the diaphragm seals against for bubble tight shutoff Restricted capacity plates...

Page 3: ...et side of the valve 8 The Capacity tag indicates the capacity of the throttle plate 100 75 50 35 in the valve NOTE On all 1 valves and 2 standard valves the throttle plate itself is stamped Item Defi...

Page 4: ...ng the pressure above the diaphragm allows the inlet pressure to progressively lift the diaphragm off the throttle plate opening the valve and satisfying the demand for flow in the downstream system R...

Page 5: ...MSS SP 61 standards If it is necessary to retest the valve follow one of the procedures listed below to prevent damage to the diaphragm OPTION 1 1 Disconnect and remove all control line s and the pil...

Page 6: ...alled in confined or enclosed spaces should be provided with adequate ventilation to prevent the possibility of gas buildup or accumulation from leaks and venting Leaks or vented gas may accumulate ca...

Page 7: ...ent valves and gauge connections are recommended in the inlet and outlet piping to the Flowgrid valve A gauge connection may be installed on the loading pressure connection to the Spring Case of the F...

Page 8: ...outlet connection on Type 30 Filter to Type 24 Restrictor inlet 3 Type 24 Restrictor mounted to Tee connection 3A Type 24 Restrictor mounted to Inlet port of Series 20 Pilot 4 Tee mounted to Inlet Por...

Page 9: ...alve 5 Sense line connecting Sense port on Series 20 Pilot to downstream piping 6 Outlet port of Series 20 Pilot connected to Outlet connection of Flowgrid valve 6A Outlet port of Series 20 Pilot conn...

Page 10: ...2 is plugged 10 Pilot cartridges in PRV mode 2nd Stage Regulator 11 Filter supply connected from inlet connection on valve body to Type 30 Filter inlet 12 Pilot supply from outlet connection on Type 3...

Page 11: ...d 9 Slowly close the downstream block valve or vent to check the Flowgrid valve for lockup shut off 10 Slowly open the downstream block valve Back Pressure Regulator or Relief Valve 1 Adjust the pilot...

Page 12: ...n the set point of the Operating Regulator becomes less than the set point of the Monitor regula tor the interstage pressure will drop from approximately full inlet pressure to 5 10 PSI above the outl...

Page 13: ...t this time 10 Raise the setpoint of Pilot 3 to verify the setpoint of the Monitor Pilot 2 Adjust if necessary Check for system stability and adjust the restrictor on Pilot 1 if required 11 Return set...

Page 14: ...sharp metal tools The bottom of the groove must have a smooth finish to prevent leakage The mating surface of adjacent parts must also be smooth to prevent leakage Assembly NOTE Do not lubricate diap...

Page 15: ...e sense line to a new location often solves control problems 4 Check to make sure needle valves are not used on any pilot system connections Full opening type valves are recommended 5 Check for pilot...

Page 16: ...O REPRE SENTATION OR WARRANTY OF ANY KIND EXPRESS OR IMPLIED AS TO MERCHANTABILITY FITNESS FOR PARTICULAR PURPOSE OR ANY OTHER MATTER WITH RESPECT TO ANY OF THE PRODUCTS While the information in this...

Reviews: