11.6.29.5 Error 30-5 (emergency code 5300h)
Cause: Error in U/f-control initialization
Suggested steps:
Check VFC parameters
This issue is probably
caused by an unsuitable
parameter setting.
l
Save your parameter set for a later restore.
l
See 'history of parameter changes' and undo
the latest changes.
l
Please check your parameter set for
implausible settings.
l
Please set device to factory setting, restart, and
see if the error occurs again.
l
When reporting this error to your service
partner, please include your device's
parameter setting.
11.6.29.6 Error 30-6 reserved
MOOG
ID No.: CB40859-001 Date: 11/2020
MSD Servo Drive - Device Help
402
11 Alarms & warnings
11.6.29.7 Error 30-7 (emergency code 5300h)
Cause: Error at lookup table (bigtab) calculation
Suggested steps:
Check settings of table configuration
This issue is probably
caused by an unsuitable
parameter setting.
l
Save your parameter set for a later restore.
l
See 'history of parameter changes' and undo
the latest changes.
l
Please check your parameter set for
implausible settings.
l
Please set device to factory setting, restart, and
see if the error occurs again.
l
When reporting this error to your service
partner, please include your device's
parameter setting.
11.6.30 Error 31: PLC error
11.6.30.1 Error 31-0 (emergency code FF00h)
Cause: User defined Error detected.
Suggested steps:
Error was triggered by PLC application (Function: MCB_CTR_SetError). Further
information is available from the programmer of the application!